Trane 3RT-PRC005-EN Air Conditioner User Manual


 
43
RT-PRC005-EN
(7½ Ton)
Standard Efficiency
Performance
Data
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-35 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2- HP Standard Motor & Drive 2-HP Standard Motor & High Static Drive
Kit (or 3-HP Oversized Motor & Drive)
2400 980 1.27 1013 1.37 1046 1.47 1076 1.57 1106 1.68 1137 1.78 1166 1.89 1194 1.99 1220 2.08 1248 2.19
2700 1010 1.49 1043 1.60 1074 1.71 1105 1.82 1134 1.93 1163 2.04 1192 2.16 1219 2.27 1246 2.39 1273 2.51
3000 1045 1.76 1076 1.87 1105 1.98 1134 2.09 1163 2.21 1192 2.34 1219 2.45 1247 2.58 1272 2.71 1299 2.84
3300 1081 2.06 1111 2.18 1141 2.30 1168 2.42 1197 2.55 1222 2.66 1249 2.79 1276 2.92 1301 3.06 1326 3.19
3600 1116 2.39 1148 2.53 1177 2.66 1204 2.79 1232 2.93 1257 3.05 1283 3.19 1309 3.32
3-HP Oversized Motor & Drive
Table PD-35 — Belt Drive Evaporator Fan Performance — 7½ Ton — TSC090,092A3,A4,AW,AK — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive (1) 2-HP Standard Motor & Drive
2400 652 0.54 701 0.63 750 0.72 794 0.81 834 0.90 873 0.98 909 1.08 945 1.17
2700 652 0.63 699 0.70 743 0.79 787 0.89 830 0.99 871 1.09 908 1.19 943 1.29 977 1.39
3000 656 0.71 703 0.81 747 0.91 789 0.99 827 1.10 867 1.20 906 1.31 944 1.43 980 1.54 1013 1.65
3300 713 0.93 755 1.03 797 1.15 836 1.24 873 1.34 908 1.45 944 1.57 980 1.69 1016 1.82 1050 1.94
3600 771 1.19 809 1.29 848 1.42 885 1.53 921 1.63 954 1.74 986 1.87 1019 1.99 1052 2.13 1085 2.26
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-36 — Belt Drive Evaporator Fan Performance — 7½ Ton — TSC090,092A3,A4,AW,AK — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 673 0.56 718 0.63 769 0.72 814 0.82 855 0.90 893 0.98 929 1.08 965 1.18 999 1.29
2700 702 0.68 738 0.76 773 0.83 817 0.92 862 1.02 904 1.13 941 1.23 975 1.32 1009 1.42 1041 1.52
3000 771 0.91 805 1.00 837 1.08 870 1.17 912 1.26 951 1.38 989 1.51 1025 1.62 1056 1.72 1088 1.82
3300 842 1.19 873 1.29 903 1.38 930 1.47 963 1.57 1000 1.68 1037 1.80 1073 1.94 1106 2.08 1136 2.19
3600 913 1.53 942 1.63 970 1.74 996 1.84 1021 1.94 1052 2.04 1086 2.16 1121 2.29 1153 2.44 1184 2.59
3-HP Oversized Motor
& Drive
2-HP Standard Motor & High Static Drive Kit (or 3-HP Oversized Motor)
2-HP Standard Motor & Field Supplied Low Static Drive (1)
Table PD-36 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & High Static Drive Kit
2-HP Standard Motor & Drive (or 3-HP Oversized Motor & Drive)
2400 1035 1.39 1070 1.50 1104 1.60 1137 1.70 1168 1.81 1201 1.92 1232 2.03 1261 2.14 1291 2.26 1319 2.38
2700 1073 1.64 1104 1.76 1136 1.87 1167 1.99 1198 2.11 1228 2.22 1258 2.34 1287 2.46 1315 2.58 1343 2.69
3000 1117 1.93 1146 2.05 1176 2.17 1205 2.31 1233 2.44 1261 2.56 1289 2.69 1317 2.82 1344 2.95 1372 3.08
3300 1165 2.30 1194 2.41 1220 2.52 1248 2.66 1275 2.79 1301 2.93 1326 3.07 1352 3.22 1378 3.36
3600 1215 2.73 1242 2.86 1269 2.98 1295 3.10 1319 3.22 1345 3.35 ———————
3-HP Oversized Motor & Drive