Trane 3RT-PRC005-EN Air Conditioner User Manual


 
64 RT-PRC005-EN
Electrical
Data
Table ED-1 — Unit Wiring — Standard Efficiency
Optional
Standard Indoor Fan Motor Oversize Indoor Fan Motor Belt Drive Indoor Fan Motor
2
Unit Minimum Maximum Fuse Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range Ampacity Circuit Breaker
1
Ampacity Circuit Breaker
1
Ampacity Circuit Breaker
1
TSC036A1 187-253 25.3 40 27.7 40 N/A N/A
3 TSC036A3 187-253 17.9 25 20.3 30 20.6 30
TSC036A4 414-506 9.2 15 10.4 15 10.6 15
TSC036AW 517-633 7.7 15 8.3 15 8.3 15
TSC048A1 187-253 34.0 50 36.1 50 N/A N/A
TSC048A3 187-253 23.9 35 26.0 40 25.3 35
4 TSC048A4 414-506 12.8 20 14.4 20 13.6 20
TSC048AW 517-633 9.8 15 10.6 15 10.0 15
TSC060A1 187-253 47.3 60 49.0 60 N/A N/A
TSC060A3 187-253 31.5 50 33.2 50 30.3 45
5 TSC060A4 414-506 16.0 25 16.3 25 15.6 25
TSC060AW 517-633 12.2 15 12.8 20 11.8 15
TSC060AK 342-418 19.6 30
TSC072A3 187-253 32.7 50 34.0 50
6 TSC072A4 414-506 17.6 25 18.2 25
TSC072AW 517-633 12.8 20 13.6 20
TSC072AK 342-418 23.2 35
TSC090A3 187-253 42.7 60 45.8 60
TSC090A4 414-506 22.6 35 24.1 35
TSC090AW 517-633 17.6 25 18.8 25
TSC090AK 342-418 28.4 40 29.9 45
TSC092A3 187-253 38.9 50 42.0 50
TSC092A4 414-506 20.5 25 22.0 25
TSC092AW 517-633 15.5 20 16.7 20
TSC102A3 187-253 45.1 60 48.2 60
TSC102A4 414-506 24.0 30 25.5 35
TSC102AW 517-633 19.5 25 20.7 25
TSC102AK 342-418 32.6 40 35.6 45
TSC120A3 187-253 52.6 60 56.6 70
10 TSC120A4 414-506 26.9 35 28.9 35
TSC120AW 517-633 21.8 25 23.5 30
TSC120AK 342-418 32.6 40 35.6 45
Notes:
1. HACR breaker per NEC.
2. Optional Belt Drive motor applies to 3-5 ton models only. The standard motor for 6-10 ton models is belt drive.
(Standard
Efficiency)