72 RT-PRC005-EN
Electrical
Data
(High
Efficiency)
Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 575 Volts — High Efficiency, continued
Standard Indoor Motor Oversize Indoor Motor
To Use Heater Heater Control Max Fuse Size or Max Fuse Size or
Tons With Model No. kW Rating
1
Stages MCA Max Circuit Breaker
2
MCA Max Circuit Breaker
2
575 Volts Three Phase
BAYHTRRW06A 6.0 1 8.6 15 9.3 15
3 THC036AW BAYHTRRW12A 12.0 2 15.8 20 16.6 20
BAYHTRRW18A 17.4 2 22.3 25 23.1 25
BAYHTRRW06A 6.0 1 9.1 15 10.1 15
4 THC048AW BAYHTRRW12A 12.0 2 16.3 20 17.3 20
BAYHTRRW18A 17.4 2 22.8 25 23.8 25
BAYHTRRW06A 6.0 1 11.8 15 12.4 15
BAYHTRRW12A 12.0 2 17.1 20 17.8 20
5 THC060AW BAYHTRRW18A 17.4 2 23.6 25 24.3 25
BAYHTRRW23A 23.0 2 30.3 35 31.0 35
BAYHTRSW09A 9.0 1 13.5 20 14.3 20
6 THC072AW BAYHTRSW18A 18.0 1 23.8 25 24.8 25
BAYHTRSW27A 27.0 2 34.6 35 35.6 40
BAYHTRSW36A 36.0 2 45.4 50 46.4 50
BAYHTRTW18A 18.0 1 24.8 25 26.3 30
7½ THC092AW BAYHTRTW27A 27.0 2 35.6 40 37.1 40
BAYHTRTW36A 36.0 2 46.4 50 47.9 50
BAYHTRTW18A 18.0 1 24.8 25 26.3 30
8½ THC102AW BAYHTRTW27A 27.0 2 35.6 40 37.1 40
BAYHTRTW36A 36.0 2 46.4 50 47.9 50
BAYHTRTW18A 18.0 1 26.3 30 28.4 30
10 THC120AW BAYHTRTW27A 27.0 2 37.1 40 39.3 40
BAYHTRTW36A 36.0 2 47.9 50 50.0 50
BAYHTRTW54A 54.0 2 56.6 60 58.8 70
Notes:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.