Trane 3RT-PRC005-EN Air Conditioner User Manual


 
37
RT-PRC005-EN
Performance
Data
(3, 4, 5 Ton)
Standard Efficiency
Table PD-24— Direct Drive Evaporator Fan Performance 3, 4 and 5 Ton TSC036A, TSC048A, TSC060A
External Static Pressure (Inches of Water) & Motor Power (Bhp)
1
Standard Motor Oversized Motor
Unit High Speed Low Speed High Speed Low Speed
Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP
960 0.81 0.36 0.61 0.28 0.96 0.39 0.89 0.35
1020 0.77 0.37 0.57 0.28 0.94 0.41 0.86 0.47
1080 0.73 0.38 0.50 0.29 0.91 0.43 0.82 0.39
1140 0.69 0.39 0.42 0.29 0.88 0.44 0.77 0.40
3 TSC036A 1200 0.66 0.40 0.34 0.30 0.84 0.45 0.74 0.41
Horizontal 1260 0.60 0.41 0.26 0.30 0.80 0.46 0.70 0.42
1320 0.55 0.42 0.14 0.31 0.75 0.48 0.65 0.44
1380 0.49 0.42 0.05 0.31 0.70 0.49 0.59 0.45
1440 0.44 0.43 0.64 0.52 0.54 0.48
1280 0.93 0.53 0.81 0.47 1.20 0.67 0.99 0.56
1360 0.87 0.54 0.75 0.47 1.15 0.68 0.94 0.58
1440 0.80 0.54 0.68 0.48 1.10 0.70 0.88 0.60
1520 0.73 0.55 0.60 0.48 1.05 0.73 0.81 0.63
4 TSC048A 1600 0.66 0.55 0.51 0.49 1.00 0.75 0.74 0.64
Horizontal 1680 0.57 0.56 0.38 0.49 0.95 0.78 0.65 0.66
1760 0.47 0.56 0.23 0.50 0.90 0.82 0.50 0.68
1840 0.37 0.57 0.13 0.50 0.83 0.83 0.35 0.70
1920 0.27 0.57 0.75 0.85 0.25 0.73
1600 0.90 0.78 0.82 0.64 1.20 0.90 1.05 0.85
1700 0.85 0.82 0.68 0.65 1.15 0.94 0.95 0.89
1800 0.80 0.85 0.56 0.65 1.05 0.98 0.85 0.91
1900 0.70 0.88 0.46 0.65 0.98 1.02 0.75 0.94
5 TSC060A
3
2000 0.60 0.90 0.30 0.66 0.90 1.05 0.65 0.95
Horizontal 2100 0.50 0.93 0.14 0.66 0.80 1.10 0.50 0.96
2200 0.40 0.95 0.05 0.67 0.70 1.12 0.35 0.96
2300 0.30 0.97 0.60 1.17 0.15 0.97
2400 0.20 1.00 0.48 1.20
960 0.86 0.36 0.61 0.28 1.01 0.39 0.89 0.35
1020 0.82 0.37 0.62 0.28 0.99 0.41 0.91 0.47
1080 0.78 0.38 0.55 0.29 0.96 0.43 0.87 0.39
1140 0.74 0.39 0.47 0.29 0.93 0.44 0.82 0.40
3 TSC036A 1200 0.71 0.40 0.39 0.30 0.89 0.45 0.79 0.41
Downflow 1260 0.65 0.41 0.31 0.30 0.85 0.46 0.75 0.42
1320 0.60 0.42 0.19 0.31 0.80 0.48 0.70 0.44
1380 0.54 0.42 0.10 0.31 0.75 0.49 0.64 0.45
1440 0.49 0.43 0.69 0.52 0.59 0.48
1280 0.98 0.53 0.86 0.47 1.25 0.67 1.04 0.56
1360 0.92 0.54 0.80 0.47 1.20 0.68 0.99 0.58
1440 0.85 0.54 0.73 0.48 1.15 0.70 0.93 0.60
1520 0.78 0.55 0.65 0.48 1.10 0.73 0.86 0.63
4 TSC048A 1600 0.71 0.55 0.56 0.49 1.05 0.75 0.79 0.64
Downflow 1680 0.62 0.56 0.43 0.49 1.00 0.78 0.70 0.66
1760 0.52 0.56 0.28 0.50 0.95 0.82 0.55 0.68
1840 0.42 0.57 0.18 0.50 0.88 0.83 0.40 0.70
1920 0.32 0.57 0.80 0.85
1600 0.95 0.78 0.87 0.64 1.25 0.90 1.10 0.85
1700 0.90 0.82 0.73 0.65 1.20 0.94 1.00 0.89
1800 0.85 0.85 0.61 0.65 1.10 0.98 0.90 0.91
1900 0.75 0.88 0.51 0.65 1.03 1.02 0.80 0.94
5 TSC060A
3
2000 0.65 0.90 0.35 0.66 0.95 1.05 0.70 0.95
Downflow 2100 0.55 0.93 0.19 0.66 0.85 1.10 0.55 0.96
2200 0.45 0.95 0.10 0.67 0.75 1.12 0.40 0.96
2300 0.35 0.97 0.65 1.17 0.20 0.97
2400 0.25 1.00 0.53 1.20
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
Notes:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.
3. YSC060AK uses a 1.0 hp direct drive motor and 12x11 FC centrifugal blower wheel. Refer to oversized motor column for the standard motor
performance data.