Trane 3RT-PRC005-EN Air Conditioner User Manual


 
50 RT-PRC005-EN
(6 Ton)
High Efficiency
Performance
Data
Table PD-48— Belt Drive Evaporator Fan Performance — 6 Ton — THC072A3,A4,AW* — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 588 0.35 643 0.43 693 0.50 738 0.57 782 0.65 823 0.73 862 0.81 900 0.89
2160 564 0.37 618 0.44 672 0.52 721 0.60 765 0.68 806 0.76 847 0.85 885 0.93 922 1.02
2400 602 0.47 652 0.54 701 0.63 750 0.72 794 0.81 834 0.90 873 0.98 909 1.08 945 1.17
2640 589 0.50 642 0.59 690 0.67 734 0.76 779 0.85 822 0.95 864 1.05 901 1.15 936 1.24 971 1.34
2880 634 0.63 682 0.74 728 0.82 770 0.91 810 1.01 851 1.11 892 1.22 930 1.33 965 1.44 999 1.54
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-48 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & High Static Drive Kit
Motor & Drive (or 2 HP Oversized Motor & Drive)
1920 937 0.98 971 1.06 1004 1.14 1037 1.22 1068 1.30 1097 1.38 1127 1.47 1154 1.55 1182 1.64 1210 1.74
2160 957 1.12 991 1.21 1024 1.30 1057 1.40 1087 1.49 1117 1.58 1146 1.67 1174 1.76 1201 1.85 1227 1.95
2400 980 1.27 1013 1.37 1046 1.47 1076 1.57 1106 1.68 1137 1.78 1166 1.89 1194 1.99 1220 2.08 1248 2.19
2640 1004 1.44 1036 1.55 1067 1.65 1098 1.77 1129 1.88 1158 1.99 1185 2.10 1214 2.22
2880 1030 1.64 1061 1.75 1092 1.86 1123 1.98 1151 2.09 1181 2.22 ———————
2-HP Oversized Motor & Drive
Table PD-49 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & High Static Drive Kit
Motor & Drive (or 2 HP Oversized Motor & Drive)
1920 990 1.05 1026 1.14 1062 1.24 1096 1.33 1130 1.43 1160 1.52 1190 1.61 1218 1.71 1247 1.80 1273 1.90
2160 1010 1.21 1047 1.31 1082 1.40 1116 1.50 1150 1.61 1182 1.71 1211 1.81 1242 1.92 1271 2.03 1298 2.14
2400 1035 1.39 1070 1.50 1104 1.60 1137 1.70 1168 1.81 1201 1.92 1232 2.03 1261 2.14 1291 2.26
2640 1065 1.59 1097 1.71 1129 1.82 1161 1.93 1192 2.05 1223 2.16 1252 2.27
2880 1099 1.80 1130 1.93 1159 2.05 1188 2.18 1217 2.30 ————
2-HP Oversized Motor & Drive
Table PD-49 — Belt Drive Evaporator Fan Performance — 6 Ton — THC072A3,A4,AW — Horizontal Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 580 0.33 641 0.41 692 0.47 738 0.54 783 0.63 827 0.71 870 0.79 912 0.88 951 0.96
2160 578 0.37 623 0.43 679 0.51 731 0.59 775 0.67 817 0.74 857 0.83 896 0.93 935 1.02 974 1.12
2400 633 0.49 673 0.56 718 0.63 769 0.72 814 0.82 855 0.90 893 0.98 929 1.08 965 1.18 999 1.29
2640 688 0.64 725 0.71 762 0.79 808 0.87 853 0.98 894 1.09 931 1.17 966 1.26 1000 1.36 1032 1.47
2880 743 0.81 778 0.90 811 0.98 848 1.06 891 1.16 932 1.28 970 1.40 1004 1.49 1037 1.59 1068 1.69
2-HP Oversized
Motor & Drive
1-HP Standard Motor & High Static
Drive Kit (or 2-HP Oversized Motor)
2-HP Oversized Motor &
Field Supplied Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due
to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
2. Field Supplied Fan Sheave AK54 and Belt AX30.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty
will not be affected.