Trane 3RT-PRC005-EN Air Conditioner User Manual


 
53
RT-PRC005-EN
(8½ Ton)
High Efficiency
Performance
Data
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 2720 CFM
Electric heaters restricted on applications below 2720 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2720 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. BAYLSDR009A Required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-52— Belt Drive Evaporator Fan Performance — 8½ Ton — THC102A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Low Static Drive Accessory Kit (1)
1700* 481 0.26 533 0.35 578 0.44 621 0.54 661 0.64 700 0.74 736 0.85 770 0.96
2040* 511 0.34 562 0.43 608 0.52 649 0.63 686 0.74 722 0.85 757 0.97 791 1.09
2380* 496 0.33 545 0.42 592 0.52 637 0.63 678 0.74 716 0.86 751 0.98 784 1.11 815 1.24
2720 539 0.44 584 0.53 626 0.64 668 0.76 708 0.88 746 1.00 781 1.12 814 1.26 845 1.40
3060 583 0.58 626 0.68 665 0.78 703 0.90 740 1.04 775 1.17 810 1.30 843 1.44 875 1.58
3400 628 0.72 669 0.84 706 0.96 741 1.08 775 1.21 809 1.36 841 1.51 873 1.65 904 1.81
3400 641 0.81 677 0.92 713 1.04 749 1.17 781 1.30 813 1.43 845 1.58 875 1.73 905 1.89 935 2.06
4080 693 1.03 726 1.15 758 1.27 792 1.41 824 1.56 854 1.69 883 1.83 912 1.99 940 2.16 968 2.33
2-HP Standard Motor & Drive
Table PD-52 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
1700* 802 1.07 833 1.19 864 1.32 893 1.45 921 1.59 948 1.72 972 1.86 998 2.01 1022 2.15 1045 2.30
2040* 823 1.21 854 1.34 884 1.47 913 1.60 940 1.73 967 1.87 993 2.01 1018 2.16 1043 2.32 1068 2.48
2380* 846 1.37 876 1.51 906 1.65 934 1.79 962 1.93 988 2.08 1014 2.22 1038 2.37 1064 2.53 1087 2.69
2720 874 1.54 904 1.69 930 1.84 958 2.00 983 2.14 1010 2.30 1035 2.46 1060 2.62 1084 2.78 1109 2.95
3060 905 1.73 933 1.89 960 2.05 986 2.20 1010 2.37 1035 2.54 1059 2.71 1083 2.89 1107 3.06 1131 3.24
3400 933 1.96 962 2.11 990 2.27 1016 2.44 1041 2.62 1065 2.79 1089 2.97 1112 3.15 1134 3.34
3400 964 2.22 992 2.39 1018 2.55 1045 2.72 1071 2.90 1095 3.08 1118 3.26 1141 3.45
4080 995 2.51 1023 2.69 1048 2.86 1075 3.05 1100 3.23 1124 3.41 ———————
3-HP Oversized Motor & Drive