Trane 3RT-PRC005-EN Air Conditioner User Manual


 
47
RT-PRC005-EN
Performance
Data
(3 Ton)
High Efficiency
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 960 CFM
Electric heaters restricted on applications below 960 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase
Heaters are required on applications below 960 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/
accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR006A Required.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
Table PD-42 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
600* 924 0.40 962 0.45 997 0.49 1031 0.54 1065 0.59
720* 943 0.45 980 0.50 1016 0.55 1050 0.60 1082 0.65
840* 962 0.50 999 0.55 1034 0.60 1068 0.66 1103 0.71
960 978 0.54 1016 0.60 1052 0.66 1086 0.72 1120 0.78
1080 995 0.59 1033 0.65 1069 0.71 1103 0.78 1136 0.84
1200 1015 0.65 1051 0.71 1086 0.77 1120 0.84 1154 0.91
1320 1036 0.72 1072 0.78 1106 0.85 1138 0.91 1171 0.98
1440 1060 0.80 1094 0.86 1128 0.93 1160 1.00 1192 1.07
1-HP Standard Motor & Field
Supplied High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 960 CFM
Electric heaters restricted on applications below 960 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 960 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Data does not include pressure drop due to reheat coil.
Refer to Table PD-61 to determine additional static pressure drop due to other options/
accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR006A Required.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
Table PD-42 — Belt Drive Evaporator Fan Performance — 3 Ton — THC036A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Low Static Drive Accessory Kit (1) 1-HP Standard Motor & Drive
600* 449 0.06 525 0.09 593 0.12 653 0.16 707 0.20 757 0.23 802 0.27 845 0.31 885 0.36
720* 475 0.08 547 0.11 612 0.14 669 0.18 724 0.22 774 0.26 821 0.31 864 0.35 905 0.40
840* 501 0.10 572 0.13 634 0.17 690 0.21 742 0.25 791 0.29 837 0.34 881 0.39 922 0.44
960 528 0.12 599 0.16 658 0.20 713 0.24 763 0.29 810 0.33 855 0.38 898 0.43 939 0.49
1080 557 0.15 625 0.19 685 0.24 738 0.28 786 0.33 832 0.38 876 0.43 917 0.48 957 0.54
1200 588 0.19 652 0.23 712 0.28 764 0.33 811 0.38 856 0.43 898 0.48 939 0.54 978 0.59
1320 552 0.18 622 0.23 681 0.27 738 0.32 790 0.38 838 0.44 882 0.49 923 0.55 962 0.60 1000 0.66
1440 588 0.23 657 0.28 713 0.33 765 0.37 817 0.43 865 0.50 909 0.56 949 0.62 987 0.68 1024 0.74
Table PD-43— Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
600* 958 0.45 996 0.50 1032 0.55 1068 0.60 1102 0.66
720* 978 0.49 1016 0.55 1053 0.61 1087 0.66 1121 0.72
840* 1002 0.55 1039 0.60 1076 0.67 1109 0.72 1143 0.79
960 1032 0.62 1066 0.67 1101 0.73 1133 0.79 1166 0.86
1080 1065 0.70 1099 0.76 1132 0.82 1164 0.89 1194 0.95
1200 1099 0.80 1133 0.86 1166 0.93 1197 0.99 1227 1.06
1320 1132 0.88 1167 0.96 1200 1.04 1230 1.11 1261 1.19
1440 1164 0.97 1199 1.05 1232 1.14 1263 1.22 1294 1.30
1-HP Standard Motor &
Field Supplied High Static Drive (2)
Table PD-43— Belt Drive Evaporator Fan Performance — 3 Ton — THC036A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Low Static Drive Accessory Kit (1) 1-HP Standard Motor & Drive
600* 493 0.07 567 0.11 628 0.14 683 0.18 737 0.22 786 0.26 832 0.30 876 0.35 918 0.40
720* 427 0.06 523 0.09 599 0.13 662 0.17 716 0.21 766 0.25 811 0.29 856 0.34 899 0.39 940 0.44
840* 460 0.08 555 0.12 631 0.16 694 0.21 750 0.25 799 0.30 844 0.35 886 0.39 925 0.44 965 0.49
960 493 0.10 588 0.15 661 0.19 725 0.24 782 0.29 832 0.35 878 0.40 919 0.46 958 0.51 996 0.56
1080 531 0.13 622 0.18 694 0.24 756 0.29 813 0.34 864 0.40 910 0.46 954 0.52 993 0.59 1031 0.65
1200 570 0.17 654 0.23 727 0.28 787 0.34 843 0.40 895 0.46 942 0.52 986 0.59 1026 0.66 1064 0.73
1320 610 0.22 687 0.28 760 0.34 821 0.40 875 0.46 925 0.53 973 0.59 1017 0.66 1058 0.73 1095 0.81
1440 651 0.27 723 0.33 793 0.40 855 0.47 908 0.53 956 0.60 1003 0.67 1047 0.75 1088 0.82 1127 0.89
1-HP Standard Motor &
Field Supplied High Static Drive (2)