Trane 3RT-PRC005-EN Air Conditioner User Manual


 
45
RT-PRC005-EN
(10 Ton)
Standard Efficiency
Performance
Data
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-40— Belt Drive Evaporator Fan Performance — 10 Ton — TSC120A3,A4,AW,AK — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive (1)
3200 730 1.00 771 1.13 807 1.26 844 1.39 886 1.55 926 1.72 965 1.89 1000 2.06
3600 729 1.13 761 1.22 792 1.32 829 1.45 865 1.60 898 1.74 930 1.89 965 2.06 1002 2.24 1038 2.43
4000 802 1.52 833 1.63 860 1.73 890 1.86 923 2.01 956 2.17 986 2.32 1015 2.48 1044 2.65 1077 2.85
4400 876 1.99 905 2.12 931 2.24 955 2.35 983 2.49 1014 2.66 1045 2.84 1072 3.01 1098 3.18 1125 3.36
4800 950 2.56 977 2.70 1002 2.84 1025 2.96 1048 3.08 1074 3.24 1102 3.43 1131 3.63 1156 3.81 1181 4.00
3-HP Standard Motor & Drive
5-HP Oversized Motor & Drive
Table PD-40 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 1029 2.20 1057 2.35 1084 2.49 1108 2.63 1132 2.77 1155 2.91 1177 3.05 1198 3.18 1219 3.32 1239 3.46
3600 1072 2.62 1106 2.81 1134 2.98 1160 3.15 1185 3.31 1209 3.47 1231 3.63 1252 3.78 1274 3.94 1295 4.10
4000 1111 3.05 1143 3.26 1174 3.47 1204 3.68 1232 3.88 1260 4.09 1283 4.27 1306 4.46 1327 4.63 1349 4.81
4400 1152 3.55 1182 3.76 1211 3.99 1241 4.21 1270 4.44 1299 4.68 1327 4.91 1352 5.14 1377 5.37 1400 5.57
4800 1205 4.19 1229 4.39 1253 4.58 1280 4.81 1309 5.06 1336 5.31 1363 5.56
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-39 — Belt Drive Evaporator Fan Performance — 10 Ton — TSC120A3,A4,AW,AK — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive (1)
3200 718 0.97 754 1.10 789 1.25 822 1.38 856 1.53 887 1.67
3600 731 1.08 764 1.20 797 1.33 829 1.48 860 1.63 892 1.79 922 1.95
4000 715 1.09 747 1.21 782 1.35 814 1.49 844 1.63 874 1.77 903 1.93 932 2.09 960 2.27
4400 741 1.27 773 1.40 803 1.53 834 1.67 864 1.82 894 1.98 922 2.13 948 2.28 975 2.44 1001 2.62
4800 803 1.62 833 1.76 861 1.90 887 2.04 916 2.20 945 2.38 972 2.55 997 2.71 1022 2.87 1046 3.04
3-HP Standard Motor & Drive
Table PD-39 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 917 1.82 945 1.97 973 2.14 999 2.30 1024 2.47 1048 2.65 1072 2.82 1095 3.00 1117 3.17 1140 3.36
3600 951 2.11 979 2.27 1007 2.43 1033 2.60 1059 2.78 1082 2.95 1107 3.14 1130 3.33 1152 3.52 1173 3.71
4000 988 2.44 1015 2.62 1042 2.79 1068 2.97 1093 3.15 1117 3.33 1142 3.52 1164 3.70 1187 3.91 1209 4.11
4400 1028 2.81 1053 3.00 1078 3.19 1103 3.38 1128 3.57 1152 3.77 1176 3.96 1198 4.15 1221 4.36 1243 4.56
4800 1071 3.23 1095 3.42 1119 3.62 1142 3.83 1166 4.04 1189 4.25 1212 4.46 1233 4.66 1256 4.88 1277 5.09
5-HP Oversized Motor & Drive