Trane 3RT-PRC005-EN Air Conditioner User Manual


 
49
RT-PRC005-EN
Performance
Data
(5 Ton)
High Efficiency
Table PD-47 — Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Low Static Drive Accessory Kit (1) 1-HP Standard Motor & Drive
1000* 507 0.11 599 0.16 671 0.21 735 0.26 792 0.31 843 0.37 889 0.42 931 0.48 971 0.54 1007 0.59
1200* 570 0.17 654 0.23 727 0.28 787 0.34 843 0.40 895 0.46 942 0.52 986 0.59 1026 0.66 1064 0.73
1400* 638 0.25 711 0.31 782 0.38 844 0.44 896 0.51 946 0.58 993 0.65 1037 0.72 1078 0.79 1117 0.86
1600 707 0.35 774 0.42 837 0.50 898 0.57 953 0.65 1001 0.72 1045 0.80 1087 0.87 1129 0.95 1168 1.03
1800 778 0.48 840 0.56 897 0.64 953 0.72 1008 0.81 1058 0.89 1102 0.98 1143 1.06 1181 1.15 1219 1.23
2000 850 0.65 908 0.73 961 0.81 1012 0.90 1062 1.00 1111 1.09 1157 1.19 1198 1.28 1237 1.37 1274 1.47
2200 923 0.84 978 0.93 1028 1.02 1075 1.12 1120 1.22 1166 1.32 1211 1.43
2400 997 1.07 1049 1.17 1096 1.27 1140 1.37 1183 1.48 ———————
Table PD-47 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1000* 1042 0.65 1078 0.70 1110 0.76 1142 0.82 1175 0.89
1200* 1099 0.80 1133 0.86 1166 0.93 1197 0.99 1227 1.06
1400* 1153 0.94 1188 1.02 1221 1.10 1253 1.18 1284 1.27
1600 1206 1.12 1241 1.20 1275 1.28 1306 1.37 1338 1.46
1800 1256 1.32 1291 1.41 1326 1.50
2000
2200
2400
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 1600CFM
Electric heaters restricted on applications below 1600 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase
Heaters are required on applications below 1600 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/
accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008A Required.
2. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
Table PD-46— Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & 1-HP Standard Motor & Low Static Drive Accessory Kit (1) 1-HP Standard
Low Static Drive Accessory Kit (1) Motor& Drive
1000* 537 0.13 608 0.17 667 0.21 721 0.25 770 0.30 817 0.35 861 0.39 905 0.45 944 0.50
1200* 517 0.15 588 0.19 652 0.23 712 0.28 764 0.33 811 0.38 856 0.43 898 0.48 939 0.54 978 0.59
1400* 576 0.21 645 0.26 702 0.31 756 0.36 808 0.41 856 0.48 900 0.54 941 0.59 979 0.65 1017 0.71
1600 640 0.31 703 0.36 757 0.41 806 0.47 854 0.52 899 0.58 944 0.65 985 0.73 1023 0.79 1060 0.86
1800 706 0.42 760 0.47 815 0.54 861 0.60 904 0.66 947 0.72 988 0.78 1028 0.86 1067 0.94 1104 1.02
2000 773 0.57 821 0.62 873 0.69 918 0.76 958 0.83 998 0.90 1036 0.96 1073 1.02 1111 1.10 1147 1.19
2200 840 0.75 885 0.80 930 0.87 977 0.95 1016 1.03 1053 1.10 1089 1.17 1124 1.24 1158 1.31 1191 1.39
2400 909 0.96 950 1.02 990 1.08 1034 1.16 1074 1.25 1110 1.00 1143 1.42 1177 1.50
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 1600 CFM
Electric heaters restricted on applications below 1600 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 1600 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/
accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008A Required.
2. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
Table PD-46 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1000* 985 0.56 1021 0.62 1058 0.68 1093 0.74 1126 0.80
1200* 1015 0.65 1051 0.71 1086 0.77 1120 0.84 1154 0.91
1400* 1052 0.77 1088 0.84 1121 0.90 1153 0.97 1185 1.04
1600 1093 0.92 1126 0.99 1160 1.06 1190 1.13 1222 1.20
1800 1138 1.10 1171 1.17 1203 1.25 1232 1.32 1262 1.39
2000 1182 1.28 1215 1.37 1246 1.46
2200 1226 1.48
2400