General
Data
(3 - 5 Ton)
High Efficiency
Table GD – 3 — General Data
3 Ton 4 To n 5 Ton
Convertible Units Convertible Units Convertible Units
THC036A1,A3,A4,AW THC048A1,A3,A4,AW THC060A1 THC060A3,A4,AW
Cooling Performance
1
Gross Cooling Capacity 38,000 49,800 62,100 62,400
SEER
/ EER
2
12.5/— 12.0/— 11.8/— 12.0/ —
Nominal CFM / ARI Rated CFM 1,200/1,200 1,600/1,600 2,000/2,000 2,000/2,000
ARI Net Cooling Capacity 36,600 47,500 59,000 59,500
System Power (kW) 3.33 4.48 5.73 5.56
Compressor
No./Type 1/Climatuff Scroll 1/Climatuff Scroll 1/Climatuff Scroll 1/Climatuff Scroll
Outdoor Sound Rating (dB)
3
83 85 84 84
Outdoor Coil — Type Lanced Lanced Lanced Lanced
Tube Size (in.) O.D. 0.3125 0.3125 0.3125 0.3125
Face Area (sq ft) 7.19 9.59 10.96 10.96
Rows/FPI 2/17 3/17 3/17 3/17
Indoor Coil — Type Lanced Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125 0.3125
Face Area (sq ft) 6.68 6.68 7.71 7.71
Rows/FPI 3/16 4/16 4/16 4/16
Refrigerant Control Short Orifice Short Orifice Short Orifice Short Orifice
9
Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT 1/¾ NPT 1/¾ NPT
Outdoor Fan — Type Propeller Propeller Propeller Propeller
No. Used/Diameter (in.) 1/22 1/22 1/22 1/22
Drive Type/No. Speeds Direct/1
10
Direct/1
10
Direct/1 Direct/1
10
CFM 2550 3050 3170 3370
No. Motors/HP 1/.20 1/.33 1/.33 1/.33
Motor RPM 1115 1115 1115 1115
Direct Drive Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used 1 1 1 1
Diameter x Width (in.) 10 x 10 11 x 11 11 x 11 11 x 11
Drive Type/No. Speeds Direct/2 Direct/2 Direct/2 Direct/2
No. Motors 1 1 1 1
Motor HP (Standard/Oversized) .33/.50 .60/.80 .90/1.00 .90/1.00
Standard Motor RPM (Low/High Speed) 950/1060 930/1000 985/1100 985/1100
Oversized Motor RPM (Low/High Speed) 1100/1145 1000/1100 1080/1135 1080/1135
Motor Frame Size (Standard/Oversized) 48/48 48/48 48/48 48/48
Belt Drive Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal
No. Used 1 1 1
Diameter x Width (in.) 11 x 11 11 x 11 11 x 11
Drive Type/No. Speeds Belt/Variable Speed
6
Belt/Variable Speed
6
Belt/Variable Speed
No. Motors 1 1 1
Motor HP 1.00 1.00 1.00
Standard Motor RPM 1750 1750 1750
Motor Frame Size 56 56 56
Filters — Type Furnished
7
Throwaway Throwaway Throwaway Throwaway
(No.) Size Recommended (in.) (2) 20 x 25 x 1 (2) 20 x 25 x 1 (2) 20 x 30 x 1 (2) 20 x 30 x 1
11
Optional Hot Gas Reheat Coil- Type
12
Lanced Lanced Lanced
Tube Size (in.) OD 0.375 0.375 0.375
Face Area (sq. ft) 2.22 2.22 2.22
Rows/FPI 1/16 1/16 2/16
Refrigerant Charge (Lbs of R-22)
4
Standard 5.3
8
7.7
5
7.9 8 .4
Optional Hot Gas Reheat Coil 5.3 8.5 10.7
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,
which is based on ARI Standard 210/240.
2. EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-60.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 8.1.
6. Belt Drive Motor is not available for THC036A1, THC048A1.
7. Optional 2” Pleated Filters also available.
8. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 4.5.
9. TXV is supplied from the factory as standard with the Dehumidification (Hot Gas Reheat) option.
10. With Dehumidification (Hot Gas Reheat) option: Direct/2 speed.
11. 2" pleated filters is a factory installed option. 2" pleated filters is standard with the Dehumidification (Hot Gas Reheat) option.
12.Available on three-phase only.