Trane 3RT-PRC005-EN Air Conditioner User Manual


 
54 RT-PRC005-EN
(8½ Ton)
High Efficiency
Performance
Data
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 2720 CFM
Electric heaters restricted on applications below 2720 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2720 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. BAYLSDR009A Required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-53 — Belt Drive Evaporator Fan Performance — 8½ Ton — THC102A3,A4,AW —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Low Static Drive Accessory Kit (1)
1700* 473 0.24 542 0.32 591 0.40 633 0.47 672 0.55 707 0.62 742 0.70 774 0.77 807 0.86
2040* 513 0.32 575 0.42 634 0.53 679 0.62 719 0.71 754 0.80 787 0.89 817 0.97 846 1.06
2380* 509 0.36 562 0.45 612 0.54 666 0.66 719 0.78 763 0.90 800 1.01 832 1.11 863 1.21 893 1.32
2720 570 0.52 612 0.60 660 0.71 703 0.81 751 0.95 798 1.09 841 1.23 877 1.36 909 1.48 939 1.60
3060 631 0.72 667 0.80 709 0.91 750 1.03 788 1.15 830 1.29 873 1.45 914 1.62 951 1.77 983 1.92
3400 692 0.96 726 1.05 760 1.15 800 1.29 836 1.42 870 1.56 907 1.71 945 1.88 984 2.06 1020 2.24
3740 754 1.26 786 1.36 815 1.46 850 1.59 886 1.74 918 1.88 949 2.03 980 2.19 1015 2.37 1052 2.57
4080 817 1.61 848 1.72 874 1.83 903 1.95 935 2.10 968 2.26 998 2.42 1026 2.58 1054 2.75 1085 2.94
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Table PD-53 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
1700* 839 0.94 869 1.03 898 1.12 926 1.21 953 1.30 980 1.40 1005 1.49 1031 1.59 1054 1.68 1078 1.78
2040* 876 1.16 903 1.25 930 1.34 957 1.44 984 1.54 1010 1.64 1036 1.75 1061 1.86 1084 1.96 1108 2.07
2380* 920 1.42 946 1.52 973 1.63 998 1.73 1021 1.83 1047 1.95 1069 2.05 1093 2.16 1115 2.27 1138 2.39
2720 967 1.72 994 1.84 1018 1.96 1042 2.07 1066 2.19 1089 2.31 1112 2.43 1134 2.55 1155 2.67 1176 2.79
3080 1012 2.06 1039 2.19 1065 2.32 1090 2.46 1113 2.59 1136 2.73 1158 2.86 1179 2.99 1199 3.12 1220 3.26
3400 1052 2.41 1083 2.58 1109 2.73 1135 2.88 1159 3.04 1183 3.19 1204 3.33
3740 1086 2.77 1119 2.96 1149 3.15 1178 3.34 ———————
4080 1117 3.14 1151 3.36 ———————
3-HP Oversized Motor & Drive