III. Indoor unit
2. Specification
III
32
2-8. Ceiling type
(1) 50Hz
Model
Power supply
Remark
Performance
Power
Others
Size
Function /
Option
Cooling
Heating
Cooling (High/Low)
Heating (High/Low)
Type
Output
Air flow rate
Cooling
Heating
Cooling
Heating
Liquid
Gas
Drain
Capacity
Sound Level
Fan output
Running current
Power input
Connecting pipe
Net weight
Shipping weight
Net dimension
(WxHxD)
Shipping dimension
(Carton/Case) (WxHxD)
Auto restart
Auto change over
Centralized controller (On/Off)
Group/Individual control from R/C
Troubleshooting by L.E.D
Auto swing (Up/Down)
Max. installation ceiling height
Drain pump
Certifications
AVMFC052EA0 AVMFC070EA0 AVMFH052EA0 AVMFH070EA0
1, 220 ~ 240, 50
18000
5.2
-
-
43/40
-
Cross fan
51
14
0.77
-
145
-
9.52
15.88
32
28
33
1200x200x650
1350x350x980
No
No
Yes (Option)
Yes (Option)
Yes
Yes
260
Option
24000
7.0
-
-
45/40
-
Cross fan
53
18
0.78
-
150
-
9.52
15.88
32
28
33
1200x200x650
1350x350x980
No
No
Yes (Option)
Yes (Option)
Yes
Yes
260
Option
18000
5.2
19000
5.6
43/40
43/40
Cross fan
51
14/14.5
0.77
0.77
145
145
9.52
15.88
32
28
33
1200x200x650
1350x350x980
Yes
No
Yes (Option)
Yes (Option)
Yes
Yes
260
Option
24000
7.0
26000
7.6
45/40
45/40
Cross fan
53
18/18.5
0.78
0.78
150
150
9.52
15.88
32
28
33
1200x200x650
1350x350x980
Yes
No
Yes (Option)
Yes (Option)
Yes
Yes
260
Option
Cooling only Heat pump
Btu/h
kW
Btu/h
kW
dB
dB
-
Watt
m
3
/min
A
A
Watt
Watt
mm
mm
mm
kg
kg
mm
mm
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
mm
Yes/No
-
ø, V, Hz
✻ 1) Indoor temperature : 27ºC DB, 19ºC WB / Outdoor temperature : 35ºC DB, 24ºC WB / Piping length : 10m, difference : 0m
✻ 2) Indoor temperature : 20ºC DB, 19ºC WB / Outdoor temperature : 7ºC DB, 6ºC WB / Piping length : 10m, difference : 0m
✻ 3) Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
✻ 1)
✻ 2)
✻ 3)
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 32