Samsung 3759 Air Conditioner User Manual


 
IV. Outdoor unit
3. Functional parts and safety devices
IV
10
Item Code Name
RVMH050CBM0
RVMH080GAM0RVMH060GDM0
Motor output
Compressor safety OLP
Crank case heater
Fan motor
Safety thermostat
High pressure switch
Low pressure switch
Thermistor (discharge)
Thermistor (condenser center)
Thermistor (condenser outlet)
Thermistor (outdoor temperature)
Suction senser
Oil senser
Thermistor (fixed discharge)
Solenoid valve
(for compressor operation)
Solenoid valve
(for bypass of high temperature gas)
Solenoid valve (liquid injection)
Solenoid valve (for exhaust air)
Solenoid valve (for capacity control)
Solenoid valve (for capacity control)
4-way valve
Check valve
open temp.
trip current
model
output
on
off
RVMH060GBM0
ZRD72KC-TFD
4.5kW
145°C
48A
90W
OSME1596SRC
128W + 128W
150°C
100°C
ZRD49KC-PFV
3.7kW
120°C
37A
90W
-
138W + 138W
135°C
90°C
ZRD72KCE-TFD
4.5kW
145°C
48A
90W
OSME1596SRC
128W + 128W
150°C
100°C
ZRDU13MC-TFD
4.2kW + 3.5kW
155°C
70A
90W
OSME4506SRC
450W
150°C
100°C
OFF : 30(±1)kg/cm
2
ON : 22(±1)kg/cm
2
OFF : 1.2(±0.2)kg/cm
2
ON : 2.2(±0.2)kg/cm
2
Model : 0166-01, Rt=150°C, 25°C=86
103AT (25°C=10k)
103AT (25°C=10k)
103AT (25°C=10k)
103AT (25°C=10k)
103AT (25°C=10k)
204CTB (25°C=200k)
Coil : Copeland (Part # 023-0028-03)
Body : EPV-1530D
Coil : Siginomiya
Body : NEV-603D
Coil : Siginomiya
Body : NEV-202D
-
-
CCH
Motor
HPS
LPS
DTS
CMS
COS
OATS
SUC.S
OIL.S
FDTS
PWM
HGBV
LBV
VBV
BV1
BV2
4-W/V
C/V
Compressor
Safety
devices
Temperature
sensor
Functional
parts
-
-
-
-
-
-
-
-
Coil & Body : JAPAN RANCO VH-60100
Fujikoki (30kg/cm
2
)
Coil & Body : JAPAN
RANCO VH-61100
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 10