V. Installation
6. Wiring
V
24
MCCB
ELB ELB
MCCB MCCB
Power supply
single
phase
3 phase 3 wire
electrical
component box
indoor unit power
supply cable
single phase AC
220V supply cable
3 phase power
supply cable
communication
cable
clamp
A part
B part
When using 3 phase and single phase ELB, cut off the wires of A and B parts.
Power supply (1 phase)
Max/Min (V) Power cablePower supply
Communication cable
(VCTF, 2wires)
Earth wire
Home server
(VCTF, 2wires)
220V / 60Hz
220-240V/50Hz
208-230V/60Hz
200-220V/50Hz
± 10% V 0.75~1.25mm
2
0.75~1.25mm
2
1.6mm
(IV, 1wire)
2.0mm
2
(CV, 2wires)
Power supply
Outdoor
unit
5.0HP
or less
3
phase
1
phase
3 phase single phase
earth
wire
communi-
cation cable
(VCTF,
2wires)
3 Phase and single phase ELB application
Power
supply
Max/Min
(V)
MCCB ELB
power
cable
wire
length
Power
supply
Max/Min
(V)
MCCB ELB
power
cable
380V/60Hz
380-415V/50Hz
± 10% V
Frame:30A
Trip:20A
20A
6.0~8.0
HP
208-230V/60Hz
380V/60Hz
380-415V/50Hz
± 10% V
Frame:50A
Trip:30A
30A
less than
16m
16~26m
3.5mm
2
,
CV, 3wires
5.5mm
2
,
CV, 3wires
less than
18m
18~28m
5.5mm
2
,
CV, 3wires
8.0mm
2
,
CV, 3wires
15A
-
15A
2.0mm
2
,
CV,
2wires
1.6mm,
IV,
1wire
2.0mm,
IV,
1wire
0.75~1.25mm
2
0.75~1.25mm
2
1.6mm
1v, 1wire
220V/60Hz
220-240V/50Hz
208-230V/60Hz
200-220V/50Hz
± 10%
volt
indoor unit
The power supply cable shall be connected to the power supply terminal and shall be fixed with
clamp as in the following figure.
The unbalance of power shall be within 2% of power supply rating.
- If the power supply unbalance is great, the lifetime of condenser is shortened.
- If the power supply unbalance exceeds 4%, the indoor unit stops and error mode displays.
10.0HP
208-230V/60Hz
460V/60Hz
380V/60Hz
380-415V/50Hz
± 10% V
Frame:75A
Trip:50A
50A
less than
18m
18~28m
8.0mm
2
,
CV, 3wires
14.0mm
2
,
CV, 3wires
5.0HP
220V/60Hz
220-240V/50Hz
208-230V/60Hz
200-220V/50Hz
± 10% V
Frame:75A
Trip:50A
50A
less than
10m
10~20m
8.0mm
2
,
CV, 2wires
14.0mm
2
,
CV, 2wires
6-2. Cable specification for outdoor unit
6-3. Connection cord specification
6-4. Wiring diagram