106 Aries User Guide
DMTIC
Continuous Current
Type
Motor
Product Rev
Syntax
<a_>DMTIC<r>
Aries 1.0
Units
r = Amps-RMS
Range
Ø.ØØ to 2ØØ.ØØ : ±Ø.Ø1
Default
Ø.ØØ (DMTIC of Ø results in motor configuration
warning)
Response
DMTIC: <*>6.5Ø
See Also
DMTICD, DMTIP, DMTR, TCI, TDICNT, TDIMAX
Auto-Setup: When using a Parker motor and the Aries Support Tool, this
command is automatically set for the selected motor.
If you did not use the Aries Support Tool, are using non-Parker motors, or
sent an RFS command to the drive, the parameter is set to zero (0)—you
must manually set this parameter to a non-zero number. Otherwise, the drive
reports the configuration errors EØ–Motor Configuration Error and
E8–Continuous Current = Ø.
For a list of automatically configured commands, see DMTR.
The DMTIC command sets the continuous operating current for a motor.
Rotary motors: The internal winding temperature will reach 125°C with a
specified heatsink in a 40°C ambient—for Parker motors only.
Linear motors: The winding will reach 90°C in a 25°C ambient—for Parker
motors only.
For heatsink dimensions, see pages 28, 29 and 30.
Example
DMTIC5 ; Set the motor current to 5 amps rms (equates to
; 7.Ø7 amps peak)
DMTICD
Continuous Current Derating
Type
Motor
Product Rev
Syntax
<a_>DMTICD<i>
Aries 1.0
Units
I = Percent derating at rated speed
Range
Ø.ØØ to 1ØØ.ØØ : ±Ø.Ø1
Default
Ø.ØØ (DMTICD of Ø results in no current derating)
Response
DMTICD: <*>5
See Also
DMTIC, DMTIP, DMTIP, DMTR, DMTW, TCI, TDICNT,
TDIMAX
Auto-Setup: When using a Parker motor and the Aries Support Tool, this
command is automatically set for the selected motor.
If you did not use the Aries Support Tool, are using non-Parker motors, or
sent an RFS command to the drive, the parameter is set to zero (0)—you
must manually set this parameter to a non-zero number.
For a list of auto-configured commands, see DMTR.