2-8
2. Processes and functions
1
2
3
Defrost control
Defrost sequence
Heating operation
(25-minute mask)
Frost detection
Defrost start
(reverse cycle defrost)
Defrost in progress
Defrost cancel
Start-up operation
Operating frequency: 61.8 Hz
Outdoor unit fan: OFF
Electronic control valve: step 300
4-way valve: OFF
Indoor unit fan: OFF
Defrost control
(1) Frost detection
1. Outdoor heat exchanger temperature (C1) method (15-minute mask after operation start)
2. Outdoor air temperature is 7°F or above and outdoor heat exchanger temperature (C1) of 0°F or below is
detected continuously for 20 seconds.
3. Outdoor air temperature is below 7°F and outdoor heat exchanger temperature (C1) of below (outdoor air
temperature -10)°F is detected continuously for 20 seconds.
(2) Defrost cancel
• Defrost end conditions
1. Outdoor heat exchanger temperature (C1) rises to 54°F or higher.
2. Outdoor heat exchanger temperature is 45°F or higher continuously for 1 minute.
3. Defrost time of 10 minutes has elapsed.
(3) Startup operation
After defrost ends, the compressors and outdoor unit fan stop for approximately 40 seconds, then operation begins
in heating mode.
2