Panasonic R410A Air Conditioner User Manual


 
1-95
1. Specifications
Fig. 1-73 shows an example of installation.
6-24. Installing the Drain Piping
(1) Prepare standard hard PVC pipe for the drain and
use the supplied hose band to prevent water leaks.
The PVC pipe must be purchased separately.
When doing this, leave a gap between the drain
socket of the unit and the PVC pipe to allow the
drainage to be checked. The transparent drain
pipe allows you to check drainage. (Fig. 1-74)
(2) After connecting the drain piping securely, wrap
the supplied packing and drain pipe insulator
around the pipe, then secure it with the supplied
clamps. (Fig. 1-75)
NOTE
Make sure the drain pipe has a downward gradient
(1/100 or more) and that there are no water traps.
CAUTION
Tighten the hose clamps so
their locking nuts face upward.
(Fig. 1-74)
Air outlet duct
Air-outlet grille
Ceiling material Indoor unit
Bolt anchor
Suspension bolt
Air-intake duct
Air-intake grille
Drain hose
(supplied)
Packing
(supplied)
Transparent part for
checking drainage
Hose band
(supplied)
Drain hose
adapter
(supplied)
Hard PVC pipe
(not supplied)
Adhere with
PVC adhesive.
Fig. 1-74
Drain insulator (supplied)
Clamps (supplied)
Fig. 1-75
Fig. 1-73
1