36 Interrupt Function and Pulse Catch Function
36.8 Pulse width/Pulse period measurement function [M8075 to M8079, D8074 to D8097]
31
FNC277-FNC279
Data
Transfer 3
32
FNC280-FNC289
High-Speed
Processing 2
33
FNC290-FNC299
Extension File
Register Control
34
FNC300-FNC305
FX
3U
-CF-ADP
35
SFC•STL
Programming
36
Interrupt
Function
37
Special Device
38
Error Code
A
Version Up
Information
B
Execution Times
*1. The ring counter offers 32-bit data including the most significant bit.
The DSUB (FNC21) instruction does not give a correct value because it handles the most significant bit as the
sign bit. To obtain a correct value, add the processing inside the dotted frame.
2. Cautions on use
• The pulse width/pulse period measurement function and input interrupts can be used at the same time in the same
input terminal.
• When the same input terminal is used by the pulse width/pulse period measurement function and the SPD
(FNC56), DSZR (FNC150) or ZRN (FNC156) instruction, an operation error occurs when the instruction is
executed.
• The input terminal used for the pulse width/pulse period measurement function cannot be used for the pulse catch
function.
• When the same input terminal is used by the pulse width/pulse period measurement function and a high-speed
counter, a grammatical error occurs.
• Make sure that the total frequency of four input channels is 50 kHz or less when using the pulse width/pulse period
measurement function.
• When the pulse width/pulse period measurement function and a high-speed counter are used together, the overall
frequency of the high-speed counter is affected.
→ For details on high-speed counters, refer to Subsection 4.7.7.