36.7 Pulse Catch Function [M8170 to M8177]
If the EI instruction is anywhere in the sequence program, the pulse catch function is always enabled. When an input
relay X000 to X007 turns from OFF to ON, a special auxiliary relay M8170 to M8177 is immediately set to ON by
interrupt processing.
The EI (FNC 04) instruction is not required in FX
3S/FX3G/FX3GC PLCs.
1. Assignment of input numbers and special auxiliary relays
*1. Cleared when the PLC mode is changed from STOP to RUN.
*2. This function is supported only in FX
3U/FX3UC PLCs.
2. Program example
*3. When using the pulse catch function at 5 µs or when receiving a pulse whose response frequency is 50 k to
100 kHz using a high-speed counter, perform the following:
- Make sure that the wiring length is 5 m or less.
- Connect a bleeder resistor of 1.5 k (1 W or more) to the input terminal, and make sure that the load current
of the open collector transistor output in the counterpart equipment is 20 mA or more including the input
current in the main unit.
3. Cautions on use
1) When receiving an input again, it is necessary to reset the device which was once set using a program.
Accordingly, until a device is reset, a new input cannot be received.
2) When it is necessary to receive continuous short pulses (input signals), use the external input interrupt function or
high-speed counter function.
3) A filter adjustment program is not required.
4) The pulse catch function is executed regardless of the operations of the special auxiliary relays M8050 to M8055
for disabling interrupts.
Pulse catch input Pulse catch relay
X000
M8170
*1
X001
M8171
*1
X002
M8172
*1
X003
M8173
*1
X004
M8174
*1
X005
M8175
*1
X006
M8176
*1*2
X007
M8177
*1*2
M8170
X002
Reset input
RST M8170
Y000
When the rising edge of X000 is detected,
M8170 is set as interrupt.
The pulse catch result is reset.
FNC 04
EI
Step
0
The EI (FNC 04) instruction is not required in FX
3S
/FX
3G
/FX
3GC
PLCs.
Input pulse width
EI
X000(Input)
M8170
X002(Reset)
PLC Input number
Input
pulse width
FX
3S
X000, X001 10 µs or more
X002 to X005 50 µs or more
FX
3G/FX3GC
X000, X001,
X003, X004
10 µs or more
X002, X005 50 µs or more
FX3U/FX3UC
X000 to X005
5 µs
*3
or more
X006, X007 50 µs or more