15 External FX I/O Device – FNC 70 to FNC 79
15.9 FNC 78 – FROM / Read From A Special Function Block
15.9 FNC 78 – FROM / Read From A Special Function Block
Outline
This instruction reads the contents of buffer memories (BMF) in a special function unit/block attached to a PLC.
When a large capacity of buffer memory (BFM) data is read by this instruction, a watchdog timer error may occur.
When bad effect is not given to the control even if data to be read is divided, use RBFM (FNC278) instruction.
For RBFM (FNC278) instruction, refer to Section 31.1.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (FROM and FROMP)
For the common items between FROM instruction and TO instruction,
refer to Subsection 15.9.1.
Special extension unit/block (BFM) PLC (word device)
"n"-point 16-bit data starting from the buffer memory (BFM) # m2 inside a special function unit/block No. m1 are
transferred (read) to "n"-point 16-bit data starting from inside a PLC.
Operand Type Description Data Type
m1
Unit number of a special extension unit/block
(K0 to K7 from the right side of the main unit)
16- or 32-bit binary
m2 Transfer source buffer memory (BFM) number 16- or 32-bit binary
Transfer destination device number 16- or 32-bit binary
n Number of transfer points 16- or 32-bit binary
Oper-
and
Type
Bit Devices Word Devices Others
System User Digit Specification System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
XYMTCSD
.b KnX KnY KnM KnS T C D R
U\G
V Z Modify K H E "
"P
m1  
m2  
 
n  
P
FNC 78
FROM
D
16-bit Instruction
9 steps
Mnemonic Operation Condition
Continuous
Operation
Pulse (Single)
Operation
FROM
FROMP
DFROM
DFROMP
Mnemonic Operation Condition
32-bit Instruction
17 steps
Continuous
Operation
Pulse (Single)
Operation
D
D
D
Command
input
FNC 78
FROM
m1 m2 n
Unit No.
m1 = 0 to 7
Transfer source BFM#
(Special extension unit/block)
m2 = 0 to 32766
Transfer destination (PLC)
Number of transfer points
n = 1 to 32767
D