2) When the nesting structure is adopted
When using MC instructions inside MC instruction, increase the nest level "N" in turn in the way "N0 N1 N2
N3 N4 N5 N6 N7".
For returning from the nesting structure, reset the nest levels from the highest one in turn using MCR instruction in
the way "N7 N6 N5 N4 N3 N2 N1 N0".
For example, if "MCR N5" is programmed without programming "MCR N6" and "MCR N7", the nest level is
returned to 5 immediately.
Available nest levels are from N0 to N7 (eight layers).
[B]
[A]
[C]
[B]
While X000
is OFF
[A]
N 1
N 2
X000
MC N 0 M100
N 0 M100
X001
Y000
X002
MC N 1 M101
N 1 M101
X003
Y001
X004
MC N 2 M102
N 2 M102
X005
Y002
MCR N 2
X006
Y003
MCR N 1
X007
Y004
MCR N 0
X010
Y005
N 0
N 1
N 2
N 0
[D]
[C]
While
X002 is
OFF
While
X004
is OFF
Circuit program
Level N0
The bus line B is active while X000 is ON.
Level N1
The bus line C is active while both X000 and
X002 are ON.
Level N2
The bus line D is active while all of X000,
X002 and X004 are ON.
Level N1
The bus line returns to the status of the bus
line C by "MCR N2".
Level N0
The bus line returns to the status of the bus
line B by "MCR N1".
Initial status
The bus line returns to the initial status of the
bus line A by "MCR N0". Accordingly, Y005
turns ON or OFF by turning ON or OFF of
X010 regardless of X000, X002 and X004.