Metrologic Instruments MX001 Sewing Machine User Manual


 
5
C
ONFIGURING THE
MX001
FOR
115
OR
230
V
OLT
O
PERATION
Before applying power to the MX001, it must first be configured for either
115 or 230 volt operation as required. This is accomplished by using the
voltage selector switch and the installation of the proper fuses. Refer to one
of the procedures on the following pages that apply to your voltage requirement
to learn which fuses should be inserted into the F1 and F2 fuse holders. (Refer to
Figure 3)
If fuse replacement becomes necessary, replace with the same type of fuse
originally supplied. Damage to the unit may result if the same type of fuse is not
used.
USA: 115V Operation
1. Move the voltage selector to the right with a small screwdriver so that the
115V legend shows in the window.
2. Open the fuse kit and remove the following:
(2) Gray Fuse Holder Caps
(1) 10 Amp 250V Fast Acting ¼ x 1 ¼ Inch Fuse
(1) 1/8 Amp 250V Slow Blow ¼ X 1 ¼ Inch Fuse
3. Press the end of the 10 Amp fuse into one of the gray fuse holder caps until
it seats.
4. Insert the fuse and cap into the F1 TRIAC fuse holder with the screwdriver
slot pointing toward the power transformer.
5. Using a small screw driver, press the cap down into the fuse holder body
and turn the cap ¼ turn clockwise to lock the cap in place. This results in the
cap slot pointing toward the top and bottom of the box.
115V
230V
F2
Control
F1
TRIAC
Fi
g
ure 3