Metrologic Instruments MX001 Sewing Machine User Manual


 
18
S IN
-
S IN+
+12V OUT
Figure 10
A IN+
A IN-
COMMON
1
2 3 4 5
6
J1
1
S SET UP 6
Figure 11
S
ENSOR
S
UPPORT
Low Voltage Self-Contained DC Sensors with a Current Sinking
Output
1. Make sure power is not being applied to the unit.
2. Open the terminals in the sensor terminal block by turning each screw
counterclockwise until there is enough space to insert wires.
3. Strip off 2 ¼ inches of the sensor cable’s outer jacket.
4. Strip the insulation off each cable wire ¼ of an inch.
5. Feed the sensor cable through the small strain relief.
6. Inserts the sensor’s DC common wire into the COMMON terminal and
secure the wire by turning the terminals’s screw clockwise. (Refer to the
MX001 box or to Figure 10 for the order of the terminals for the sensor
wires.)
7. Insert and secure the sensor’s +DC power input wire into the +12V OUT
terminal.
8. Insert and secure the sensor’s signal output wire into the S IN- terminal.
9. Secure the cable by turning the strain relief’s domed sealing nut clockwise
until tight.
10. Position the jumper on pins 5 and 6 of the J1 (S SET UP) header. (Refer to
Figure 11).