Greenheck Fan 470656 Fan User Manual


 
35
NOTE
The Freeze Temperature is preset to the factory
recommended 45ºF. Steps 9-11 should only
be completed if the Freeze Temperature needs
adjustment.
NOTE
The Freeze Temperature is the temperature at which
the supply solenoid closes and the drain solenoid
opens to drain the supply line, preventing possible
freeze damage. A drain solenoid is required for this
option.
9. Enter Program Mode
Press and hold
the Enter key
for three seconds. The
display will read “Pro”
when Program Mode is
active.
10. Adjust the Freeze Temperature
While in Program Mode, use the Up and Down
keys to navigate
through the
Menu Options
until “Frt” is
displayed. Press
the Enter key to access
the selected Menu
Option setting.
Use the Up and Down keys to adjust the Freeze
Temperature setting as needed. Press the Enter key to
set the Freeze Temperature and return to the Program
Menu.
Program Display
Freeze Temperature
Display
NOTE
The Enter key must be pressed to save the new
freeze temperature.
Program Mode
Program Mode allows the user to view the Program
Menu and edit the factory default settings. To access
Program Mode and view the Program Menu press and
hold the Enter key for three seconds. While viewing
the Program Menu press the Up and Down keys to
scroll through the Menu Options. To view the setting
of the selected Menu Option, press the Enter key.
To edit the setting, press the Up or Down key while
viewing the setting. To save the setting and return to
the Program Menu, press the Enter key. To return to
the Program Menu without saving the change, wait
10 seconds. To exit Program Mode from the Program
Menu, wait 10 seconds.
Operation - Water Wizard™ (optional)
CAUTION
The sump drain line must be clear and draining to a
safe location before using Flow Test Mode.
CAUTION
Be aware of the water level in the sump tank at all
times when using the Flow Test Mode.
WARNING
Changing the default settings will significantly affect
performance. Only change a setting after reading
and understanding this entire manual.
WARNING
The Enter key must be pressed to save any changes
made to a setting.
Light Status
Indicating
Light
On Off
Blinking
Long on, short off
Blinking
Short on, long off
L1
Call for
cooling
No call for
cooling
Call for cooling.
Outdoor temperature
lockout.
N/A
L2
Drain
solenoid
open
Drain
solenoid
closed
N/A
Supply solenoid open.
Drain solenoid closed.
L3
Cooling
on
Cooling
off
Supply solenoid
locked closed
Flow test mode active
Drain Mode locks open the drain solenoid
and drains the supply line between the supply
solenoid and the media. To activate Drain Mode,
simultaneously press the Function and Enter keys (L2
will light). To deactivate Drain Mode and unlock the
drain solenoid, simultaneously press the Function and
Enter keys again.
Flow Test Mode - Activating Flow Test Mode
opens the supply solenoid and allows water to pass to
the manual supply valve. To activate Flow Test Mode,
press and hold the Function key for one second (L3
will flash). To deactivate Flow Test Mode and allow the
supply solenoid to close, press and hold the Function
key again for one second.
Dry Bulb Temperature
The dry bulb temperature is visible on the home
screen. If a number is not visible, wait 15 seconds
and use the Up and Down keys until a number is
displayed.
Wet Bulb Temperature
To view the Wet Bulb Temperature, simultaneously
press and hold the Up and Down keys.
Indicating Lights
Three indicating lights are located across the top
of the display to indicate the status of the Water
Wizard™.
11. Exit Program Mode
After ten seconds of idle time the controller will exit
Program Mode.
®
Model IG / IGX Make-Up Air