Carrier 50PEC09-18 Heat Pump User Manual


 
52
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
LEGEND
SCREEN NAME POINT NAME
PASSWORD
LEVEL
EDITABLE RANGE DEFAULT NOTES
Configuration
Set Points
Occupied Heating
User/Admin
Password level
access
X 40 - 90 F 72 F
Defines the Occupied
Heating Set Point
Occupied Cooling X 55 - 99 F 76 F
Defines the Occupied
Cooling Set Point
Unoccupied Heating X 40 - 90 F 55 F
Defines the Unoccupied
Heating Set Point
Unoccupied Cooling X 55 - 99 F 90 F
Defines the Unoccupied
Cooling Set Point
Effective Heating
Set Point
X0 - 10 F
Takes into effect bias (maximum
allowable set point deviation)
Effective Cooling
Set Point
X0 - 10 F
Takes into effect bias (maximum
allowable set point deviation)
Optimal Start
Uses historical data to calculate
ramp up time so as to be at set point
at occupied/unoccupied time
Occupied RH
Set Point
X 0 - 100% 65%
Defines the control set point used
during occupied periods (Viewable
only if Humidity Sensor = Installed/
Determines when to start
Dehumidification when occupied)
Unoccupied RH
Set Point
X 0 - 100% 90%
Defines the control set point used
during unoccupied periods
(Viewable only if Humidity Sensor =
Installed/Determines when to start
Dehumidification when unoccupied)
DCV CTRL Start
Set Point
X 0 - 9999 ppm 500 ppm
Defines the control set point used to
start increasing ventilation during
occupied periods (Viewable only if
Ventilation DMP Type = DCV)
DCV Max CTRL
Set Point
X 0 - 9999 ppm 1050 ppm
Defines the control set point
used to define where the ventilation
will reach its maximum limit during
occupied periods (Viewable only if
Ventilation DMP Type = DCV/Used
to determine DCV ending control
point)
Configuration
Schedule
Weekly Schedule
Start Time
User/Admin
Password level
access
X 00:00 - 23:59 06:00
Defines the start time for an
occupied period
End Time X 00:00 - 24:00 18:00
Defines the ending time of an
occupied period
Mon X No/Yes Yes
Determines if this day is included
in this schedule
Tu e X N o/ Yes Yes
Determines if this day is included
in this schedule
Wed X No/Yes Yes
Determines if this day is included
in this schedule
Thur X No/Yes Yes
Determines if this day is included
in this schedule
Fri X No/Yes Yes
Determines if this day is included
in this schedule
Sat X No/Yes No
Determines if this day is included
in this schedule
Sun X No/Yes No
Determines if this day is included
in this schedule
Configuration
Schedule
Exception
Schedules 1 - 12
Start Month
User/Admin
Password level
access
X0 - 120
Defines the start month of this
hoilday schedule
Start Day X 0 - 31 0
Defines the start day of this holiday
schedule
Start Time X 00:00 - 23:59 0:00
Determines the start time for this
schedule
End Month X 0 - 12 0
Defines the month to end this
hoilday schedule
End Day X 0 - 31 0
Defines the day to end this holiday
schedule
End Time X 00:00 - 24:00 0:00
Determines the time to end this
schedule
°°
°°
°°
°°
°
°
BAS Building Automation System
DCV Demand Controlled Ventilation
IAQ Indoor Air Quality
OAT Outdoor Air Temperature
RH Relative Humidity
SAT Supply Air Temperature
SPT Space Temperature
TPI Third Party Integration