Carrier 50PEC09-18 Heat Pump User Manual


 
23
AL Alarm Relay Contacts
BM Blower Motor
BR Blower Relay
CAP Capacitor
CB Circuit Breaker
CO Sensor, Condensate Overflow
CR Compressor Relay
DM Damper Motor
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
FSS Fan Speed Switch
HP High-Pressure Switch
JW1 Jumper Wire for Alarm
LOC Loss of Charge Pressure Switch
NLL Night Low Limit
OV Override
PB Power Terminal Block
PM Performance Monitor
RVS Reversing Valve Solenoid
TRANS Transformer
WV Water Valve
---------- Field Line Voltage Wiring
Field Low-Voltage Wiring
Printed Circuit Trace
Option Low Voltage Wiring
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
Mate-N-Lock
>
>
CLOSED=UNOCCUPIED
Y
G
DELUXE
D
CONTROL
BR 1
(LO)
CR
CAP
PB
GROUND
LUG
TRANSFORMER
BR 2
(HI)
COMPR.
RELAY
CCG
YEL
HP
LOC
FP1
FP2
RV
CO12
P7
24V
DC
EH1
EH2
P6
HP
LOC
FP1
FP2
RVS
CO
SEE
NOTE
4
RED
RED
BLU
BRN
GRY
GRY
VIO
VIO
BRN
ORG
NOT USED
1
2
3
4
5
6
7
8
9
10
CC
BRN
YEL
CR
1
0
STATUS
DELUXE D
MICROPROCESSOR
CONTROL LOGIC
TEST
FAULT
R
RV
RELAY
TEST
PINS
JW3
FP1 LOW
JW2
FP2 LOW
SEE
NOTE 4
JW1
LP N.O.
COM
NO
NO NC
COM
FAN
SPEED
RELAY
FAN ENABLE
RELAY
GRY
Y1
Y1
W1
O/W2
G
R
C
AL1
COMPRESSOR
COOLING
FAN
24 VAC
COMMON
ALARM
CLASS 1 WIRING
REQUIRED INSIDE
Y
O
G
R
C
X1
CLASS 1 OR 2 WIRING
ACCEPTABLE
OUTSIDE
CONTROL BOX
TYPICAL HEAT
PUMP T-STAT
SEE NOTE 5
BRN
SEE
NOTE 7
AL2
R
NSB
C
ESD
OVR
H
A
R
NO1
NC1
COM
NO2
NC2
COM
R
P1
P2
P3
RED
BRN
WHT
YEL
RED
YEL YEL YEL
BRN
BRN
ORG
DM
OV
OV
OVERRIDE
OVERRIDE
OVERRIDE
WITH DIGITAL T-STAT
TIME CLOCK
NLL
WV
ALARM
RELAY
SEE
NOTE 6
C
R
JW4
AL2 DRY
COM2 COM1
R C S
SC
1
2
3
4
5
6
7
8
ACC1
RELAY
ACC2
RELAY
BLU
S1
DIP SWITCH
PACKAGE
PM: DISABLE/
ENABLE
UNIT STAGE: 2/1
T-STAT: HEAT COOL/
HEAT PUMP
RV ON B/RV ON O
DEHUMID/NORMAL
NOT USED
BOILERLESS:
ENABLE/DISABLE
BOILERLESS:
40°F/50°F
1
2
3
4
5
6
7
8
OFF ON
S2
DIP SWITCH
PACKAGE
ACC1
FUNCTIONS
ACC2
FUNCTIONS
H: HI FAN/DEHUMID
NOT USED
1
2
3
4
5
6
7
8
OFF ON
BLK
ORG
230V
24V
TRANS
CB*
POWER SUPPLY
REFER TO DATA PLATE
USE COPPER CONDUCTORS ONLY.
SEE NOTE 2
REFER TO DISCONNECT
BOX FOR OPTIONAL
POWER SUPPLY CONNECTION
GROUND
L2
L1
OPTIONAL
CORD
CONNECTION
RED
NEUTRAL ON 265V
SYSTEMS
L2 (ribbed)
GROUND
L1 (plain)
PB
1
2
H
C
F
CAP
RED
RED
6
8
2
4
BLK
BLK
R
S
C
CR
BLU
COMPRESSOR
BRN
YEL
2
1
BM
B (HIGH)
A (LOW)
RED
BLK
115
208
230
265
WHT
RED
ORG
BRN
LEAD COLOR
VOLTAGE
TRANSFORMER PRIMARY
LEAD COLORS
YEL
SEE
NOTE 3
1
3
2
FSS
GRY
BLOWER MOTOR WIRING
UNIT SIZE POLE A POLE B
09 5 4
12 4 3
15 4 3
18 4 3
Fig. 22 — 50PEC Unit Remote-Mounted Thermostat with Deluxe D Controller Wiring
*Optional wiring.
NOTES:
1. Compressor and blower motor thermally
protected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 115-V (WHT) lead
for 115/1/60 units; 265-V (BRN) lead for 265/
1/60 units; or 208-V (RED) lead for 208/1/60
units.
For 230/1/60 operation, switch the RED and
ORG leads at L1 and insulate the RED lead.
Transformer is energy limiting or may have a
circuit breaker.
4. FP1 thermistor provides freeze protection
for WATER. When using ANTI-FREEZE
solutions, cut JW3 jumper.
5. Typical heat pump thermostat wiring shown.
Refer to thermostat Installation Instructions
for wiring to the unit.
6. 24-V alarm signal shown. For dry alarm con-
tact, cut AL2 DRY (JW4) jumper and dry
contact will be available between AL1 and
AL2.
7. Transformer secondary ground via Deluxe D
board standoffs and screws to control box.
(Ground available from top two standoffs as
shown.)
LEGEND