Carrier 50PEC09-18 Heat Pump User Manual


 
18
Fig. 17 — 50PEC Unit Manual or Auto Changeover with Complete C Controller Wiring
LEGEND
NOTES:
1. Compressor and blower motor thermally pro-
tected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 115-V (WHT) lead for
115/1/60 units; 265-V (BRN) lead for 265/1/60
units; or 208-V (RED) lead for 208/1/60 units.
For 230/1/60 operation, switch the RED and
ORG leads at L1 and insulate the RED lead.
Transformer is energy limiting or may have a
circuit breaker.
4. FP1 thermistor provides freeze protection for
WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.
5. For remote sensor, position jumper J1 on upper
2 pins.
6. For F position, position jumper on both pins.
For C, position jumper on one pin.
7. Transformer secondary ground via Complete C
board standoffs and screws to control box.
(Ground available from top two standoffs as
shown.)
8. Mate-N-Lok† plug is optional.
9. Factory-cut jumper (JW1). Dry contact will be
available between AL1 and AL2.
°
°
AL Alarm Relay Contacts
BM Blower Motor
BR Blower Relay
CAP Capacitor
CB Circuit Breaker
CO Sensor, Condensate Overflow
CR Compressor Relay
DM Damper Motor
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HP High-Pressure Switch
JW1 Jumper Wire for Alarm
LOC Loss of Charge Pressure Switch
PB Power Terminal Block
RAS Return Air Sensor
RVS Reversing Valve Solenoid
TRANS
Transformer
WV
Water Valve
---------- Field Line Voltage Wiring
Field Low-Voltage Wiring
Printed Circuit Trace
Option Low Voltage Wiring
*Optional wiring.
†Registered trademark of AMP Incorporated.
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
Mate-N-Lok
>
>
Complete C
Complete C
SEE NOTE 9
BLOWER MOTOR WIRING
UNIT SIZE POLE A POLE B
09-18 5 4