The Average Occupied Heat Set Point displays the
Occupied Heat set point from the Linkage Thermostat.
Average Occupied
Heat Set Point: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Average Occupied Cool Set Point displays the Occu-
pied Cool set point from the Linkage Thermostat.
Average Occupied
Cool Set Point: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Average Unoccupied Heat Set Point displays the Unoc-
cupied heat set point from the Linkage Thermostat.
Average Unoccupied
Heat Set Point: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Average Unoccupied Cool Set Point displays the Unoc-
cupied cool set point from the Linkage Thermostat.
Average Unoccupied
Cool Set Point: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Average Zone Temperature displays the space tempera-
ture from the Linkage Thermostat.
Average Zone
Temperature: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Average Occupied Zone Temperature displays the
space temperature from the Linkage Thermostat during occu-
pied periods.
Average Occupied
Zone Temperature: Display Units: Degrees F (Degrees C)
Display Range: 0.0 to 99.9
Default Value: 0.0
Network Access: None
The Occupancy Status point displays a 1 if occupancy is re-
ported by the Linkage Thermostat. The Occupancy Status
point displays a 0 if occupancy is not reported by the Linkage
Thermostat.
Occupancy
Status: Display Range: 0, 1
Default Value: 0
Network Access: None
Table 17 Maintenance
NOTE:
Bold
values indicate points that can be forced through communications.
DESCRIPTION VALUE UNITS STATUS FORCE NAME
Thermostat Control No TSTAT
Occupied
Yes
OCCUP
Timed Override in Effect No TIMOV
Start Bias Time 0 min STRTBIAS
Heat No HEAT
Cool No COOL
IAQ Control No IAQCL
Demand Limit No DEMLT
Temp Compensated Start No TCSTR
IAQ Pre-Occupancy Purge No IQPRG
Unoccupied Free Cool No NTFCL
Fire Shutdown
No
FIRES
Linkage Control
No
DAVCL
Field/Startup Test
No
FIELD
Heat Submaster Ref 40.0 dF SHSR
Cool Submaster Ref 150.0 dF CCSR
Economizer Submaster Ref 120.0 dF ECONSR
Economizer Submastr Gain 0.00 ECONGN
Compressor Starts 0.00 CMPST
Compressor 1 Runtime 0.00 HOURS CM1RT
Compressor 2 Runtime 0.00 HOURS CM2RT
Supply Fan Runtime 17.00 HOURS FANRT
Linkage Thermostat
Linkage Status 2 LINKSTAT
Supervisory Element 0 SUPE-ADR
Supervisory Bus 0 SUPE-BUS
Supervisory Block 0 BLOCKNUM
Average Occ Heat Setpt 0.0 dF OCLOSTPT
Average Occ Cool Setpt 0.0 dF OCHISTPT
Average Unoc Heat Setpt 0.0 dF UNLOSTPT
Average Unoc Cool Setpt 0.0 dF UNHISTPT
Average Zone Temp 0.0 dF AZT
Average Occ Zone Temp 0.0 dF AOZT
Occupancy Status(1=occ) 1 OCCSTAT