39
Low Reference specifies Low Point of the Outdoor IAQ
Sensor Range in ppm.
Low Reference: Units: PPM (parts per million)
Range: 0 to 5000
Default Value: 0
High Reference specifies High Point of the Outdoor IAQ
Sensor Range in ppm.
High Reference: Units: PPM (parts per million)
Range: 0 to 5000
Default Value: 2000
OUTDOOR AIR QUALITY LOCKOUT POINT — When
set to non-zero value, the IAQ algorithm will compare Outdoor
IAQ reading against this decision and disable IAQ control
whenever the value of OAQ exceeds this configured value.
Outdoor Air
Quality Lockout
Point: Range: 0 to 5000
Default Value: 0
SERVICE PASSWORD — The Service Password function
defines the password needed to access the controller via the
Navigator interface.
Service Password: Range: 0000 to 9999
Default Value: 1111
PASSWORD ENABLE — The Password Enable function is
used to require a password to be entered when attempting
to access the controller via the Navigator™ display module
interface.
Password
Enable: Range: Enable/Disable
Default Value: Disable
METRIC DISPLAY — The Metric Display function is used
to toggle the display for the Navigator between US and Metric
units.
Metric Display: Range: On/Off
Default Value: Off
Occupancy Maintenance Screen —
The Occupan-
cy Maintenance screen is used to check the occupied schedule.
Information concerning the current occupied period is dis-
played. See Table 16.
MODE — The Mode point displays the current occupied
mode for the controller. If the controller is following its own
local schedule this is the result of the local schedule status. If
the controller is configured to follow a global schedule, this
point displays the mode last received from a global schedule
broadcast.
Mode: Display Range: 0 to 1
Default Value: 0
Network Access: None
CURRENT OCCUPIED PERIOD — If the controller is con-
figured to determine occupancy locally, the Current Occupied
Period point is used to display the current period determining
occupancy.
Current Occupied
Period: Display Range: 1 to 8
Default Value: 0
Network Access: None
OVERRIDE IN PROGRESS — The Override in Progress
point is used to display if an occupancy override is in progress.
The point will display “Yes” if an override is in progress, or
“No” if there is no override.
Override In
Progress: Display Range: Yes/No
Default Value: No
Network Access: None
OVERRIDE DURATION — The Override Duration point
displays the number of minutes remaining for an occupancy
override which is in effect. If the override duration value down-
loaded is in hours, the value will be converted to minutes. If the
occupancy schedule is occupied when override is initiated, the
current occupancy period will be extended by the number of
hours/minutes requested.
If the current occupancy period is unoccupied when the oc-
cupancy override is initiated, the mode will change to occupied
for the duration of the number of hours/minutes downloaded. If
the occupancy override is due to end after the start of the next
occupancy period, the mode will transition from occupancy
override to occupied without becoming unoccupied, and the
occupancy override timer will be reset.
Override
Duration: Display Units: Minutes
Display Range: 0 to 240
Default Value: 0
Network Access: None
OCCUPIED START TIME — The Occupied Start Time
point shows the time that the current occupied mode began. If
the current mode is unoccupied or the controller is following a
global schedule, the value displayed by this point will remain at
default.
Occupied
Start Time: Display Range: 00:00 to 24:00
Default Value: 00:00
Network Access: None
UNOCCUPIED START TIME — The Unoccupied Start
Time point shows the time that the current occupied mode will
end. This will also be the beginning of the next unoccupied
mode. If the current mode is unoccupied or the controller is
following a global schedule, the value displayed by this point
will remain at default.
Unoccupied
Start Time: Display Range: 00:00 to 24:00
Default Value: 00:00
Network Access: None
NEXT OCCUPIED DAY — The Next Occupied Day point
displays the day of week when the next occupied period will
begin. This point is used with the Next Occupied Time so the
user will know when the next occupied period will occur. If the
controller is following a global schedule this point will remain
at default.
Next Occupied
Day: Display Range: MON, TUE, WED,
THU, FRI, SAT, SUN
Default Value: No display (Blank)
Network Access: None
NEXT OCCUPIED TIME — The Next Occupied Time point
displays the time day when the next occupied period will
begin. This point is used with the Next Occupied Day so the
user will know when the next occupied period will occur. If the
PremierLink™ controller is following a global schedule this
point will remain at default.
Next Occupied
Time: Display Range: 00:00 to 24:00
Default Value: 00:00
Network Access: None