Carrier 33CSPREMLK Air Conditioner User Manual


 
31
Table 8 Thermostat Control Input Display
ALARM RE-ALARM TIME — This decision is used to con-
figure the number of minutes that will elapse between
re-alarms. A re-alarm occurs when the condition that caused
the initial alarm continues to persist for the number of minutes
specified. Re-alarming continues to occur at the specified
interval until the alarm condition no longer exists.
Re-Alarm Time: Display Units: Minutes
Display Range: 0 to 1440
Default Value: 0 (Disabled)
CONTROL TEMPERATURE HYSTERESIS — This con-
figuration defines the range above the high set point and below
the low set point the space temperature must exceed for an
alarm condition to exist during occupied hours.
For example, if the current setpoint is 75 F and the hystere-
sis value is 5° F, an alarm will be generated if space tempera-
ture exceeds the low limit of 70 F or the high limit of 80 F.
Control
Temperature
Hysteresis: Display Units: Delta Degrees F
(Delta Degrees C)
Range: 1.0 to 100.0
Default Value: 5.0
SUPPLY AIR TEMPERATURE — HIGH LIMIT — The
Supply Air Temperature High Limit alarm is used to monitor
the value of the supply air temperature within a specified range.
If the supply air temperature becomes too high, an alarm condi-
tion will exist.
Supply Air
Temperature
High Limit: Display Units: Degrees F (Degrees C)
Display Range: –40.0 to 245.0
Default Value: 150.0
SUPPLY AIR TEMPERATURE — LOW LIMIT — The
Supply Air Temperature Low Limit alarm is used to monitor
the value of the supply air temperature within a specified range.
If the supply air temperature becomes too low, an alarm condi-
tion will exist.
Supply Air
Temperature
Low Limit: Display Units: Degrees F (Degrees C)
Display Range: –40.0 to 245.0
Default Value: 45.0
INDOOR AIR QUALITY ALERT LIMIT — The Indoor-
Air Quality Alert Limit alarm defines the allowable CO
2
levels
during occupied periods. If the CO
2
levels become too low or
too high during occupied periods, an alarm condition will exist.
Indoor Air Quality
Low Limit: Display Units: PPM (implied)
Display Range: 0.0 to 5000.0
Default Value: 0.0
Indoor Air Quality
High Limit: Display Units: PPM (implied)
Display Range: 0.0 to 5000.0
Default Value: 1200.0
Table 9 Alarm Service Configuration
Controller Identification Screen
The controller
identification screen contains reference information used to
identify the PremierLink™ controller. See Table 10.
DESCRIPTION — The Description point displays the type of
device.
LOCATION — The Location point shows the location of the
device.
SOFTWARE PART NUMBER — The Software Part Num-
ber indicates the part number of the software being used.
MODEL NUMBER — The Model Number indicates the
model number of the device being used.
SERIAL NUMBER — The Serial Number indicates the serial
number of the device being used.
REFERENCE NUMBER The Reference Number indi-
cates the version of the software being used.
Table 10 Controller Identification
*Software part number CESR131269-03 is version 1.2.
Holiday Configuration Screen
The Holiday Con-
figuration screen is used by the PremierLink controller to store
configuration fields for up to twelve holidays. See Table 11.
START MONTH — The Start Month field is used to config-
ure the month that the holiday will start. The numbers 1
through 12 are used to indicate which month is specified.
Start Month: Range: 1 to 12
Default Value: 1 (January)
START DAY — The Start Day field is used to determine
which day the holiday will start.
Start Day: Range: 1 to 31
Default Value: 1
DESCRIPTION VALUE UNITS STATUS FORCE NAME
Y1 - Call for Cool 1
On
Y1
Y2 - Call for Cool 2
On
Y2
W1 - Call for Heat 1
Off
W1
W2 - Call for Heat 2
Off
W2
G - Call for Fan
On
G
DESCRIPTION VALUE UNITS NAME
Alarm Control
Alarm Routing Control
00000000
ALRMCNT
Realarm Time
0
min REALARM
Control Temp Hysteresis
5.0
^F SPTHYS
Supply Air Temperature
Low Limit
45.0
dF LOWLIM
High Limit
150.0
dF HIGHLIM
IAQ High Alert Limit
Low Limit
0.0
LOWLIM
High Limit
1200.0
HIGHLIM
DESCRIPTION VALUE UNITS NAME
Description:
Rooftop Control
DevDesc
Location: Location
Software Part Number: CESR131269-04* PartNum
Model Number: ModelNum
Serial Number: SerialNo
Reference Number: Version 1.3 RefNum