Table 9
-
Keypad Directory (cant)
STATUS (cant)
SUBFUNCTION
I
KEYPADENTRY
6
TEMPERATURE (cant) cl
4
q
t
cl
4
cl
4
0
4
7 PRESSURE
8 ANALOG
9
1NPUTS
DISPLAY
SCTB X
SSTB X
CTB X
SHB X
RST X*
PRESSURE
DPA X
SPA X
xxxx
OPA X
DPB X
SPB X
xxxx
OPB X
ANALOG
REF X
LMT X*
RST X*
INPUT
SPW
x*
DLI
X*
DL2 X*
COMMENT
Circuit B Saturated Condenser Temperature
Circuit B Saturated Suction Temperature
Compressor Bl Suction Temperature
Circuit B Suction Superheat
Reset Temperature
Refrigerant System Pressure (psig)
Circuit A Discharge Pressure
Circuit A Suction Pressure
Circuit A Discharge/Suction
Circuit A Oil Pressure Differential
Circuit B Discharge Pressure
Circuit 8 Suction Pressure
Circuit B Discharge/Suction
Circuit B Oil Pressure Differential
Status of Analog Inputs
Transducer Supply Voltage
Demand 4-20 mA Signal
Reset 4-20
mA
Signal
Status of Switch Inputs
Dual Set Point Switch
Demand Limit Switch 1
Demand Limit Switch 2
31