BRK electronic Mx-1000 Smoke Alarm User Manual


 
15.8 Configuring the Fire Routing, Fire Protection and Fault routing O/Ps
To configure the Fire Routing Output to volt-free relay contacts, remove links J10, J11 and J12.
[These links are combined in a single block].
To configure the Fire Protection Output to volt-free relay contacts, remove links J14, J15 and J16.
[These links are combined in a single block].
To configure the Fault Routing Output to volt-free relay contacts, remove links J6, J7 and J8.
[These links are combined in a single block].
These links are located below the associated output in the top right hand section of the C1627
motherboard. See Figure 10 – C1627 Motherboard Layout
15.9 Enable/disable earth fault monitoring.
To disable the earth fault monitoring, remove the link J18 located towards the bottom right hand
corner of the C1627 motherboard. See Figure 10 – C1627 Motherboard Layout.
16 Optional Clock Module – Configuration and Setting
16.1 Standard Module Engineer Mode:
16.1.1 To Zero the Alarm Counter:
Open panel door and move the DIL switch 1, pole 2 on the clock module PCB to the ON position.
Return the DIL switch to the OFF position.
16.1.2 To Access the Engineers Clock Module Edit Functions:
Select the Access Control key switch to position “1”.
Press SELECT ON/OFF button.
Use the ↑↓ buttons to scroll the cursor LED indication through the selectable options on the panel
display LED indications until the LCD backlight illuminates. The normal time display is:
HH:MM:SS
D/N ON
or
HH:MM:SS
D/N OFF
To select Day/Night Mode On/Off:
o Press the SELECT ON/OFF button to enter Day/night mode On/Off Set Display:
D/N ON
Change?
or
D/N OFF
Change?
o On the rear of the Clock Module PCB, move the DIL switch 1, pole 1 to the ON
position. Pressing ENABLE (+) or DISABLE (-) toggles the setting between D/N
ON and D/N OFF.
To set the current time:
o Press SELECT to enter the current Time Set Display:
HH:MM:SS
Time Set
HH
flashing
Page 33 of 40