13.5 Powering up
1. Prior to powering up, the panel will have been installed in accordance with the installation
instructions, all cabling will have been fully installed and tested, glanded into the panel
enclosure but not connected to the panel terminals. The mains supply should be isolated
externally to the panel.
2. Check the battery connections are correct.
3. Remove the mains supply fuse from the panel mains terminal block. Once the permit to
energise the mains supply is in place, energise the mains and check the voltage and
polarity are correct before replacing the panel fuse.
4. The panel will power up and if all the end of line devices are correctly terminated in the
panel and the battery is OK, the panel should be silent, displaying only the Power Supply
On indication.
5. Turn the Access keyswitch to “1” and press the Test Display button. The panel should
respond by lighting all indications and sounding the buzzer. This will continue for a few
seconds after the button is released.
13.6 Configuration.
13.6.1 Basic Default Configuration
When first powered up, the Mx-1000 Series Fire Alarm Panel can be operated in the standard
default mode without any additional configuration.
The basic default mode is:
○ All zones latching fire, non-delay, standard [non-intrinsically safe]
○ Fire Routing, Fire Protection and Sounder outputs not delayed.
13.6.2 Site-Specific Configuration.
It is possible to tailor the functionality of the Mx-1000 Sereies Fire Alarm Panel in line with site-
specific requirements. Details of the site configurable options and the configuration process are
provided in sections 13.6 and 15.1 respectively. Charts are provided in the System Log Book for
planning/recording the actual configuration. This configuration is not lost when the panel is
powered down.
13.7 Commissioning Procedure
After completion of the pre-commissioning wiring check, power-up and configuration, commission
the circuits in line with the following guide.
13.7.1 Alarm Circuits
1. Remove the resistor from the first alarm circuit terminal and connect the first alarm circuit
wiring to the terminals, observing correct polarity. Check that any alarm fault indications
clear after a few seconds.
2. Use the Alarm Test facility [see Mx-1000 Series User Manual] or press Evacuate to
operate the sounders. Check that all sounders connected to the alarm circuit operate.
3. Deselect the Alarms Test condition or if “Evacuate” was used, press silence alarms to
stop the sounders operating.
4. Repeat steps 1 to 3 for the second and any subsequent alarm circuits.
Page 21 of 40