BRK electronic Mx-1000 Smoke Alarm User Manual


 
14 User Controls and Indications
14.1 User Indications [showing optional clock module]
General Indicator Section
Indicator Description Colour Operating Condition
Power Supply On Green Steady indication for Mains or Standby power On.
Fire Red Flashes on any new fire alarm condition, changing to a steady
indication on operation of Silence Alarms.
Fire Routing Active Red Steady indication when the Fire Routing Output is active.
General Fault Yellow Flashes for any fault condition.
Power Supply Fault Yellow Flashes for mains or standby power supply/charge fault
System Fault Yellow Steady indication to indicate Microcontroller or Memory Failure.
Flashes to indicate Engineer’s Configuration Mode active.
Earth Fault Yellow Flashes for any positive or negative power supply earth fault.
Fuse Fault Yellow Flashes for any auxiliary supply fuse failure
Repeater Fault Yellow Flashes for any Repeater fault or repeater communication fault,
Sounder Fault/Disabled Yellow Flashes for any sounder fault. Steady for sounders disabled.
Sounder Test Yellow Steady indication while sounder walk test is active.
Fire Protection Fault/Disabled Yellow Flashes for a fault on the Fire Protection Output. Steady when Fire
Protection Output is disabled.
Fire Routing Fault/Disabled Yellow Flashes for a fault on the Fire Routing Output. Steady when Fire
Routing Output is disabled.
Fault Routing Fault/Disabled Yellow Flashes for a fault on the Fault Routing Output. Steady when Fault
Routing Output is disabled.
POWER SUPPLY ON
FIRE
FIRE ROUTING ACTIVE
GENERAL FAULT
POWER SUPPLY FAULT
SYSTEM FAULT
REPEATER FAULT
SOUNDER TEST
FIRE ROUTING FAULT/DISABLED
EARTH FAULT
SOUNDER FAULT/DISABLED
FIRE PROTECTION FAULT/DISABLED
FAULT ROUTING FAULT/DISABLED
FUSE FAULT
EVACUATE TEST DISPLAY
SILENCE/
RESOUND
ALARMS
RESET
SILENCE
BUZZER
DELAY
ON/OFF/
OVERRIDE
SELECT
ON/OFF
ENABLE
DISABLE
TEST
SELECT
ZONE LOCATION ZONE LOCATION
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
22
21
24
23
26
25
28
27
30
29
32
31
1 0
21 : 18 : 05
D / N OFF
Zone Location Indications
Indicator Description Colour Operating Condition
User Generated Zone Location Text Red Flashes when zone is in a fire condition, turning to steady on
operation of Silence Alarms.
User Generated Zone Location Text Yellow Flashes when zone is in a fault condition. Illuminates steady
when zone is disabled or in test.
Access Controls Keyswitch:
0 – Controls Locked
1 – Controls Unlocked
User Instructions
Clock Module [Optional]:
Showing time and
Day/Night off
Back light flashes for
Clock Module fault.
Page 25 of 40