BRK electronic Mx-1000 Smoke Alarm User Manual


 
SW 1/3 – Delay On Auto:
OFF: Automatically turn off the delay mode once a day at the set time [the delay mode
first being turned on manually].
ON: Automatically turn the delay mode on once a day and off once a day at the set
times.
Requires optional clock module.
SW 1/4 - Config Non-Latch Zones:
OFF: Configuration mode disabled.
ON: Enables selected zones to be configured to non-latching fire mode via the
Engineer’s Select feature.
[Not EN54 compliant function].
SW 1/5 - Config I/S Zones:
OFF: Configuration mode disabled.
ON: Enables selected zones to be configured to Intrinsically Safe alarm thresholds and
passive end of line fault monitoring via the Engineer’s Select feature. [For use with
appropriate I.S. barriers/Isolators, typically 330 Ohm zener barriers or galvanic
isolators].
[Not EN54 compliant function. Provided to meet existing customer requirements.]
SW 1/6 - Config M/S Zones:
OFF: Configuration mode disabled.
ON: Enables selected zones to be configured to short circuit fire mode via the
Engineer’s Select feature.
SW 1/7 - Config Delay Zones:
OFF: Configuration mode disabled.
ON: Enables selected zones to be configured to Delay Mode via the Engineer’s Select
feature.
SW 1/8 - Configure Delay O/Ps:
OFF: Configuration mode disabled.
ON: Enables the selection of outputs, via the Engineer’s Select feature, to which the
panel delay will apply.
SW 1/9 - 2 Stage Delay:
OFF: Single Stage Delay Mode.
ON: Two Stage Delay Mode.
SW 1/10 - Alarms on Evac Only:
OFF: Sounders operate on any fire condition including evacuate.
ON: Selects sounders to operate only when the panel is in the evacuate condition
[Not EN54 complaint function. Provided to meet existing customer requirements.]
SW 2/1 - Silence Before Reset:
Select type of reset mode. [Not EN54 compliant function. Provided to meet existing customer
requirements]:
OFF: Reset available when panel is in the [un-silenced] fire or fault condition.
ON: Fire Condition Reset available only when panel is in Alarm Silenced condition.
Fault reset available when panel is in the fault condition.
SW 2/2 to 2/5 - Delay/Minutes:
Page 30 of 40