15.4 Engineer’s Zone/Output Configuration Time-out Warning:
This feature is provided to prevent the panel being left in the Zone/Output Configuration condition.
1 minute after the last button press:
The panel buzzer will restart.
The Select LED will flash.
The System Fault LED will continue flashing.
Press the Select On/Off button to continue with the configuration process otherwise quit
the configuration process as described in 15.2.4 above
15.5 Invalid Configuration conditions:
Invalid condition: If 2 or more configuration switches on the motherboard are in the ON
position at the same time:
The Config LED on the motherboard will flash.
The System Fault and Select LEDs on the display will flash.
The fault relay will operate.
The panel buzzer will sound.
The Cursor indication will clear.
Configuration will be inhibited.
To clear the invalid condition check the zone and output config switches [1/4, 1/5, 1/6,
1/7, 1/8] on the motherboard and ensure that only one is selected to ON.
Invalid condition: Selecting any config mode switch [1/4, 1/5, 1/6, 1/7, 1/8] to the ON
position whilst the panel is in the fire condition.
The Config LED on the motherboard will flash.
The System Fault and Select LEDs on the display will flash.
The panel buzzer will sound.
The Cursor indication will clear.
Configuration will be inhibited.
To clear the invalid condition, select the config switch to OFF. Reset the fire alarm
condition before attempting the configuration process again.
15.6 List of configuration DIL switches and their functions
SW 1/1 - Inhibit F/P on NLZ:
Selects Fire Protection relay to operate or not to operate for a fire condition on any zone
configured to non-latched mode.
OFF Fire Protection relay operates for a fire condition on any zone configured to non-
latched mode.
ON: Fire Protection relay does not operate for a fire condition on any zone configured
to non-latched mode.
[Not EN54 compliant function].
S/W 1/2 - Delay Alarm Sil & Rst:
OFF: Silence and reset available as normal.
ON: Prevents alarms being silenced or reset for a period of 3 minutes after a fire alarm
condition occurs.
[Not EN54 compliant function].