15.4 Engineer’s Zone/Output Configuration Time-out Warning:
This feature is provided to prevent the panel being left in the Zone/Output Configuration condition.
● 1 minute after the last button press:
○ The panel buzzer will restart.
○ The Select LED will flash.
○ The System Fault LED will continue flashing.
● Press the Select On/Off button to continue with the configuration process otherwise quit
the configuration process as described in 15.2.4 above
15.5 Invalid Configuration conditions:
● Invalid condition: If 2 or more configuration switches on the motherboard are in the ON
position at the same time:
○ The Config LED on the motherboard will flash.
○ The System Fault and Select LEDs on the display will flash.
○ The fault relay will operate.
○ The panel buzzer will sound.
○ The Cursor indication will clear.
○ Configuration will be inhibited.
● To clear the invalid condition check the zone and output config switches [1/4, 1/5, 1/6,
1/7, 1/8] on the motherboard and ensure that only one is selected to ON.
● Invalid condition: Selecting any config mode switch [1/4, 1/5, 1/6, 1/7, 1/8] to the ON
position whilst the panel is in the fire condition.
○ The Config LED on the motherboard will flash.
○ The System Fault and Select LEDs on the display will flash.
○ The panel buzzer will sound.
○ The Cursor indication will clear.
○ Configuration will be inhibited.
● To clear the invalid condition, select the config switch to OFF. Reset the fire alarm
condition before attempting the configuration process again.
15.6 List of configuration DIL switches and their functions
● SW 1/1 - Inhibit F/P on NLZ:
Selects Fire Protection relay to operate or not to operate for a fire condition on any zone
configured to non-latched mode.
○ OFF Fire Protection relay operates for a fire condition on any zone configured to non-
latched mode.
○ ON: Fire Protection relay does not operate for a fire condition on any zone configured
to non-latched mode.
○ [Not EN54 compliant function].
● S/W 1/2 - Delay Alarm Sil & Rst:
○ OFF: Silence and reset available as normal.
○ ON: Prevents alarms being silenced or reset for a period of 3 minutes after a fire alarm
condition occurs.
○ [Not EN54 compliant function].