25. Place the right-hand battery into the bottom of the panel. The terminals should be
positioned towards the centre of the enclosure and the battery should be adjacent to the
right side of the backbox located by the raised indents in the back box above the battery
and to the left.
26. Connect the black battery lead to the power supply “Batt -” [battery negative] terminal and
connect the red battery lead to the power supply “Batt +” [battery positive] positive
terminal [situated on the motherboard for the Mx-1002, Mx-1004, Mx-1008 and Mx-1016
panels and repeater panel or on the separate power supply board in the Mx-1032 panel].
The location of the motherboard battery terminals are shown in Figure 10 – C1627
Motherboard Layout and Figure 12 – 32-Zone Power Supply Layout. Fit the connector on
the end of the black lead onto the negative (black) terminal of the left-hand battery. Fit the
connector on the end of the red lead onto the positive (red) terminal of the right-hand
battery.
28. Connect the blue battery lead between the positive (red) terminal of the left-hand battery
and the negative (black) terminal of the right-hand battery. Note that the batteries will not
power the panel until the mains supply is energised.
12.2.2 Installation And Connection Of The C1631 Repeater Interface
Warning: Observe anti-static precautions
1. Ensure that the panel and repeaters are powered down and the main and standby
supplies are disconnected.
2. On the fire alarm panel and each repeater, remove the jumper link at J22 (adjacent to J9)
and fit a C1631 repeater interface to connectors J13 and J9 located immediately to the
left of the Zone Expansion ribbon connector on the right-hand side of the C1627
motherboard. The board should be held in place by the 12mm high plastic spacer
provided. See Figure 10 – C1627 Motherboard Layout.
3. Connect the RS485 data cable as shown in Figure 13– Repeater Connection Diagram.
4 If the repeater is powered from the panel then connect the Aux 24V d.c. supply from the
panel to the repeater.
Notes:
1. Use only RS485 screened data cable.
2. Connect the cable screen to earth only at the fire alarm panel.
Page 17 of 40