For Output Delay configuration, through Sounders, Fire Protection and Fire Routing
outputs in forward [Select↓] or reverse [Select ↑] sequence starting at Sounders.
● 3. To change the configuration of a selected zone or output:
○ With the cursor flashing on the selected zone or output:
Operation of the ENABLE button will apply the configuration functionality to the
selected zone/output causing the associated fault/disabled LED to provide a
continuous indication.
Operation of the DISABLE button will clear the configuration from the selection and
restore normal operation. The fault/disabled LED will clear.
By repeating steps 2 and 3, any number of zones [or outputs] can be configured.
● 4. To quit the programmable configuration mode:
○ To return the panel to normal operating mode applying the updated configuration:
Open the panel door and return the selected Config DIL switch on the motherboard
to the OFF position.
The CONFIG ENABLED LED on the motherboard will clear, the panel buzzer will
silence and the flashing System Fault indication and zone/output configuration
status indications on the display will clear as will the cursor and the Select
indications. Any current alarms, disablements, will be re-indicated along with any
active status indications [Delay on etc.].
○ Close and lock the panel door.
○ Return the ACCESS keyswitch to the “0” position to disable the controls on the display.
IMPORTANT NOTE: WHILE THE PANEL IS IN THE ENGINEER’S
ZONAL/OUTPUT CONFIGURATION MODE, ALL ZONAL INPUTS ARE IN
PERMANENT RESET AND OUTPUTS ARE INHIBITED – THE PANEL WILL
NOT RESPOND TO ANY FIRE ALARM.
15.3 To Restore the Factory Default Configuration for Zones &
Outputs:
● Open the panel door and locate the DIL switches SW1-4 to SW1-8 on the motherboard
[Config Non-latch Zones; Config I.S. Zones; Config M/S Zones; Config Delay Zones;
Config Delay O/Ps] and move the switch actuator on each switch to the On position.
○ The Config Enabled LED on the motherboard will flash.
○ The Panel’s System Fault LED will flash and the buzzer will operate.
○ Any standing fault or disablement indications will clear.
○ It will not be possible to enter the Select Mode.
● Press the Disable button on the panel’s display.
● Return DIL switches 1-4 to 1-8 to the OFF position.
○ The Config Enabled LED on the motherboard will clear.
○ The Panel’s System Fault LED will flash and the buzzer will clear.
○ The factory default configuration [all zones as latching fire, non-delay, standard [non-
intrinsically safe] will be restored and the Fire Routing, Fire Protection and Sounder
outputs will no longer be delayed
Page 28 of 40