ERROR DISPLAYED DESCRIPTION OF ERROR
The control is no longer able to read the heater supply sensor due to an open circuit. In
this case, if the heater outlet sensor is present and operational, the control will operate
based
on the heater outlet sensor. If the heater outlet sensor is not available and the heater
inlet sensor is present and operational, the control will operate using the heater inlet sensor.
Otherwise,
the control will not operate the heater stages.
The control is no longer able to read the heater supply sensor due to a short circuit. In this
case,
if the heater outlet sensor is present and operational, the control will operate based
on the heater outlet sensor. If the heater outlet sensor is not available and the heater inlet
sensor
is present and operational, the control will operate using the heater inlet sensor.
Otherwise,
the control will not operate the heater stages.
The control
is no longer able to read the heater inlet sensor due to an open circuit. In
this case, the control will continue operation.
The control
is no longer able to read the heater outlet sensor due to an open circuit. In
this case, if the heater inlet sensor is present and operational, the control will operate
using
the heater inlet sensor. Otherwise, the control will not operate the heater stages.
The control was unable
to read a piece of information from its EEPROM. The control will
stop operation
until all settings in the Adjust menu have been checked by the user or
inst
aller.
The control
is no longer able to read the outdoor sensor due to an open circuit. In this
case,
the control assumes an outdoor temperature of 32°F and continues operation.
The control
is no longer able to read the tank sensor due to an open circuit. In this
case
the control will not operate the heater stages.
The control
is no longer able to read the tank sensor due to a short circuit. In this case
the control will not operate the heater stages.
The control
is no longer able to read the outdoor sensor due to a short circuit. In this
case,
the control assumes an outdoor temperature of 32°F and continues operation.
The control
is no longer able to read the heater inlet sensor due to a short circuit. In
this case, the control will continue operation.
The control
is no longer able to read the heater outlet sensor due to a short circuit. In
this case, if the heater inlet sensor is present and operational, the control will operate
using
the heater inlet sensor. Otherwise, the control will not operate the heater stages.