Trane Engineered Smoke Control System for Tracer Summit Smoke Alarm User Manual


 
Selecting a mounting location
BAS-APG001-EN 55
Selecting a mounting location
Make sure that the location meets the operating environment require-
ments and clearance requirements described in the following sections.
The Tracer MP581 controller must be installed indoors. Trane recom
-
mends locating the Tracer MP581 controller in the same room (within 20
ft) of the controlled equipment to reduce wiring costs.
CAUTION
Equipment damage!
Install the Tracer MP581 in a location that is out of direct sunlight. Fail-
ure to do so may cause the Tracer MP581 to overheat.
Operating environment requirements
Make sure that the operating environment conforms to the specifications
listed in
Table 14.
Table 14. Operating environment specifications
Temperature From –40°F to 120°F (–40°C to 49°C)
Humidity 10–90% non-condensing
Altitude 6500 ft (2000 m)
High-voltage power
requirements
North America: 98–132 Vac, 1 A maximum, 1 phase
Weight Mounting surface must be able to support 25 lb (12 kg)