Trane Engineered Smoke Control System for Tracer Summit Smoke Alarm User Manual


 
BAS-APG001-EN 99
Chapter 7
Programming
Programming occurs after hardware installation is complete. The smoke
control system must be programmed for automatic response, weekly self-
testing, end-process verification, and response to manual FSCS
commands.
Response times
Time response requirements must be kept in mind when programming.
They are give in
Table 27.
The 10 second time limit mentioned in Table 27 controls how fast Tracer
Graphical Programming (TGP) programs can be run. Suggested program
rates are 2 seconds for communication watchdogs and 4–5 seconds for
control programs.
Table 27. Time response requirements
Response time Process
10 seconds (UL 864: 49.2.a)
The maximum time allowed from when an acti-
vation signal is received until a fire or smoke
safety function is initiated. An activation signal
could be from the FACP of the FSCS.
15 seconds The maximum time allowed between a feed-
back signal activation and an FSCS panel indi-
cation (either audio or LED). A feedback signal
will typically be a binary value, either hard-
wired or communicated.
60 seconds (UL 864: 49.2.c)
Fan operation proof of desired state, either on
or off.
75 seconds (UL 864: 49.2.c)
Damper position proof of desired position,
either open or closed.
200 seconds (UL 864: 49.2.b)
The maximum time allowed between determi-
nation of a failure state of critical equipment or
process and notification of that failure. A failure
state could include communication failures or
equipment problems such as a fan not starting
as commanded.