Trane Engineered Smoke Control System for Tracer Summit Smoke Alarm User Manual


 
Chapter 5 Installing the Tracer MP581 programmable controller
54 BAS-APG001-EN
Specifications
The Tracer MP581 conforms to the specifications shown in Table 13.
Table 13. Tracer MP581 specifications
Weight 15 lb (7 kg)
Operating temperature From –40°F to 120°F (–40°C to 49°C)
Storage temperature From –58°F to 203°F (–50°C to 95°C)
Humidity 10–90% non-condensing
Altitude 6500 ft (2000 m)
Installation Category 3
Pollution Degree 2
High-voltage power require-
ments
North America: 120 Vac, 1 A maximum, 1
phase
Weight Mounting surface must be able to support
25 lb (12 kg)
Analog to digital conversion
Digital to analog conversion
12 bit
12 bit
Microprocessor
Processor clock speed:
Motorola MC68332
20 MHz
Memory RAM: 256 kB (16-bit word)
EEPROM: 256 kB (8-bit word)
Flash: 1 MB (16-bit word)
Clock Crystal controlled 32.768 kHz
Battery None required