Trane Engineered Smoke Control System for Tracer Summit Smoke Alarm User Manual


 
Setting the I/O bus addresses
BAS-APG001-EN 93
Setting the I/O bus addresses
Each EX2 on the link with the Tracer MP581 must have a unique
address. Configure the address using the DIP switches on the EX2 circuit
board (
Figure 50). Table 23 shows the DIP switch settings for expansion
modules 1 through 4.
Figure 50. DIP switch on board
Input/output terminal wiring
All input/output terminal wiring for the EX2 module must meet the fol-
lowing requirements:
All wiring must be in accordance with the National Electrical Code
and local codes.
Use only 18 AWG twisted-pair wire with stranded, tinned-copper
conductors.
Binary output wiring must not exceed 20 ft (6.1 m) and must be in
conduit.
Binary input wiring must not exceed 20 ft (6.1 m) and must be in
conduit.
Analog and 24 Vdc output wiring distances depend on the specifica-
tions of the receiving unit. Use shielding for analog and 24 Vdc
outputs.
Do not run input/output wires in the same wire bundle with ac-power
wires.
Table 23. EX2 DIP switch settings
EX2 module D1 D2
1 Off Off
2 Off On
3 On Off
4 On On