BAS-APG001-EN 129
UUKL binding list (actuator failure status)
Table 35 shows an example list of actuator failure status bindings.
Actuator failure status is sent directly from the mechanical system to the
FSCP.
UUKL binding list (FSCP control)
Table 36 shows an example list of smoke control panel control custom
bindings. Smoke control panel commands affect all MP581s panel control
units.
Table 35. Actuator failure status bindings
Function Originator Network variable Destination
supplyFanFail Mechanical system nvoSwitch20 MP580-3/nviSwitch05
returnFanFail Mechanical system nvoSwitch21 MP580-4/nviSwitch04
oadamperFail Mechanical system nvoSwitch22 MP580-3/nviSwitch03
radamperFail Mechanical system nvoSwitch23 MP580-2/nviSwitch01
eadamperFail Mechanical system nvoSwitch24 MP580-4/nviSwitch02
stairFanFail Mechanical system nvoSwitch25 MP580-2/nviSwitch02
supplyDamperFloor01Fail Mechanical system nvoSwitch26 MP580-3/nviSwitch07
returnDamperFloor01Fail Mechanical system nvoSwitch27 MP580-3/nviSwitch08
supplyDamperFloor02Fail Mechanical system nvoSwitch28 MP580-3/nviSwitch10
returnDamperFloor02Fail Mechanical system nvoSwitch29 MP580-3/nviSwitch11
supplyDamperFloor03Fail Mechanical system nvoSwitch30 MP580-4/nviSwitch06
returnDamperFloor03Fail Mechanical system nvoSwitch31 MP580-4/nviSwitch07
supplyDamperFloor04Fail Mechanical system nvoSwitch32 MP580-4/nviSwitch09
returnDamperFloor04Fail Mechanical system nvoSwitch33 MP580-4/nviSwitch10
checkSupervisedCircuits Mechanical system nvoSwitch40 MP580-2/nviSwitch04
Table 36. Smoke control panel control custom bindings
Function Originator Network variable Destination
lampTest MP580-2 nvoSwitch01 MP580-3/nviSwitch40
nvoSwitch01 MP580-4/nviSwitch40
panel enable/disable MP580-2 nvoSwitch03 MP580-3/nviSwitch36
nvoSwitch03 MP580-4/nviSwitch36