<A> Make sure the pipes from the twinning pipe to the outdoor unit are
sloped downwards (towards the twinning pipes).
F
C
2m
F
D
E
C
<B> When the piping on the outdoor unit side (from the twinning pipe)
exceeds 2 m, ensure a trap (gas pipe only) within 2 m.
<C> Slope of twinning pipes
15
±
F
G
<D> Pipe connection example [EP650]
A : Downward slope
B : Upward slope
C : Indoor unit
D : Trap (gas pipe only)
E : Within 2 m
F : Twinning pipe
G :
Slope of the
twinning
pipe is at an angle within ±15° to the gro
und
H : Pipes on site
I : Twinning kit
J : Straight run of pipe that is 500 mm or more
6