Mitsubishi Electronics OC366 Air Conditioner User Manual


 
4
(4) Determine Fan Airflow setting during Indoor Thermo OFF conditions:
a) These settings are done within Indoor DIPSW1-7 and DIPSW1-8, see chart below for options.
b) Recommended SW1-7 OFF and SW1-8 ON will determine airflow based on "Setting on the remote controller".
Fan speed
setting
Fan speed
setting
OFF ON
SW1-7 SW1-8
OFF OFF Very low
ON OFF Low
OFF ON
Setting on
remote
controller
ON
ON
Stopped
Auxiliary Heating
Signal
Thermo Condition
(5) Setting Outdoor unit and Auxiliary heat switch over temperatures.
When the DIPSW 4-4 is set to "ON", the outdoor unit and the contact output operates as shown below.
a) Outdoor default setting and operations are shown below:
Stage 1
A
mb. Decreasing - Outdoor unit HP operation
Amb. Increasing - Defrost : Heater contact ON signal
- Other than defrost : Contact OFF
Stage 2
- Outdoor unit HP operation
- Heater contact ON signal
Stage 3
- Outdoor unit OFF (Standby)
- Heater contact ON signal
TH7 = Outdoor Temperature
a
-12:
[10F]
b
0:
[32F]
c
10:
[50F]
d
20:
[68F]
(3) Determine required Indoor Fans Speed during defrost mode:
0 20k 27k 39k 62K
None Black Blue White Red
Stopped
Setting on
remote
controller
Very Low Low High
Note: The setting will be disabled "when Heater contact signal is OFF".
CN22 input resistance ()
CN22 input (cable color)
FAN SPEED SETTING
OFF
Fan airflow rate setting
During defrost operation
ON
Wiring
CN22
a) With no Primary heating output the Indoor fan normally goes off to prevent cold drafts during the defrost cycles.
b) With Primary heating control the auxiliary heat will be on during defrost mode, thus cold drafts will not be present.
(Ducted units only)
c) For models PEFY and PDFY (Ducted) recommended to use "Black" (20K) connector.
d) For models PLFY, PCFY, PKFY and PFFY (Ductless) recommended "None", no connector required.
e) To set the fan airflow rate to be used during defrost operation, insert the resistance that is packed within the optional
adaptor cable kit (PAC-YU24HT-F) into the CN22 sensor input.
You can choose at what speed the indoor fan operates during defrost cycles bases on chart below.
Setting on
remote
controller