Mitsubishi Electronics OC366 Air Conditioner User Manual


 
11
4 SPECIFICATIONS
PUMY-P36NHMU(-BS) PUMY-P36NHMUR1(-BS)
Cooling Capacity Btu/h
*3
*3
*3
*3
*3
*3
*3
*3
36,000
Heating Capacity Btu/h
Btu/h/W
W/W
40,000
3.22
14.23/15.74
98.4
2.93
12.88/14.24
98.9
11.18
4.00
Input
(
Cool
)
kW
Input Current
(
Cool
)
Power factor (Cool)
A
%
%
Input
(
Heat
)
kW
Input Current
(
Heat
)
Power factor (Heat)
A
EER
(
Cool
)
COP
(
Heat
)
Connectable indoor units
(
Max.
)
6
Max. Connectable Capacity Btu/h 46,800
(
130%
)
Power Supply Single phase
,
60Hz
,
208/230V
Breaker Size
Min.Circuit.Ampacity
Max. fuse size
30A
40A
26A
Sound level
(
Cool/Heat
)
dB 49 / 51
External finish Munsell 3Y 7.8/1.1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
ANB33FDHMT ANB33FDSMT
Model
Motor output kW 2.2
Starting method Inverter
Crankcase heater W
Heat exchanger Plate fin coil
(
Anti corrosion fin treatment
)
Fan Fan
(
drive
) %
No. Propeller fan % 2
Fan motor output kW 0.086 + 0.086
Airflow m
3
/min
[
CFM] 100 [3,530]
Dimensions
(
H
%
W
%
D
)
Wmm
[
in.
]
950
[
37-13/32]
Dmm
[
in.
]
330+30
[
13+1-3/16
)
Hmm
[
in.
]
1
,
350
[
53-5/32
]
Weight kg
[
lbs
]
130 [287]
Refrigerant R410A
Charge kg
[
lbs
]
8.5
[
18.7
]
Protection High pressure protection HP switch
devices
Compressor protection
Discharge thermo,
Over current detection
Compressor thermo,
Over current detection
Fan motor protection Overheating/Voltage protection
Oil
(
Model
)
2.3 [73]
(
FV50S
)
Total Piping length
(
Max.
)
m [ft]
L [oz]
120 [394]
Farthest m [ft] 80 [262]
Max Height difference m [ft] 50 [164]*1
Chargeless length m [ft] 50 [164]
Piping diameter
Liquid :mm[inch] 9.52
[
3/8
]
Gas :mm[inch] 15.88
[
5/8
]
Guaranteed operation range
(
cool
)
-5~ 46 DB [23~115
°
F DB]*2
(
heat
)
-18~ 15 WB [0~60
°
F WB]
Item
Service Ref.
Rating conditions
Cooling Indoor : D.B. 26.7°C / W.B. 19.4°C
[D.B. 80°F / W.B. 67°F]
Outdoor : D.B. 35°C [D.B. 95°F]
Heating Indoor : D.B. 21.1°C[D.B. 70°F]
Outdoor : D.B. 8.3°C / W.B. 6.1°C
[D.B. 47°F / W.B. 43°F]
Note.*1. 20m [70ft] : In case of installing outdoor unit lower than indoor unit.
*2.
10~46°C [50~115°F]DB : In case of connecting PKFY-P06/P08 type indoor unit.
*3. Electrical data is for only outdoor unit.
(In case of connecting 2 indoor units of PLFY-P18BM type)
Btu/h=kW × 3,412 CFM=K/min × 35.31 lbs=kg/ 0.4536
*Above specification data is subject to rounding variation.