Mitsubishi Electronics OC366 Air Conditioner User Manual


 
10
3-2. UNIT SPECIFICATIONS
(1) Method for identifying MULTI-S model
Indoor unit < When using Model 30 >
Outdoor unit <When using model 48 >
(2) Operating temperature range
Notes D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
*1. 10~46°C DB [50~115°FDB] : In case of connecting PKFY-P06/P08 type indoor unit.
P L F Y - P 30 N B M U - E PU M Y - P 48 N H M U -BS
PAC type
Frequency
conversion
controller
Refrigerant
R410A/R22
commonness
Refrigerant
R410A
NEW frequency converter
one-to-many air conditioners
(flexible design type)
Indicates equivalent
to Cooling capacity
Indicates equivalent
to Cooling capacity
Power supply
N: Single phase
208/230V 60Hz
Power supply
N: Single phase
208/230V 60Hz
L : Ceiling cassette
K : Wall-mounted type
E : Hidden skylight type
C : Ceiling suspended type
M : Ceiling cassette type
F : Floor standing type
Outdoor unit
model type
Sub-number
Unit model type
UL model
M-NET control
M-NET control
UL model
Salt proof
type
Frequency
conversion
controller
Outdoor unit
MULTI-S
Cooling
W.B. 15~24°C [59~75°F]
Heating
D.B. 15~27°C [59~81°F]
W.B. -18~15°C [0~60°F]
Indoor-side intake air temperature
Outdoor-side intake air temperature
D.B. -5~46°C [23~115°F]*1
(3) Guaranteed voltage
198~253V, 60Hz
In case of connecting fresh air type indoor unit
air type indoor
Capacity of Fresh
Cooling
Heating
Indoor-side and Outdoor-side
P30
D.B.21~43[70~109°F] *2
W.B.15.5~35[60~95°F]
D.B.-10~20[14~68°F] *3
intake air temperature
P54
D.B.21~43[70~109°F] *2
W.B.15.5~35[60~95°F]
D.B.-5~20[23~68°F] *3
*2.Thermo-off(FAN-mode) automatically starts if the outdoor temp. is lower than 21D.B.[70°FD.B.].
*3.Thermo-off(FAN-mode) automatically starts if the outdoor temp. is higher than 20D.B.[68°FD.B.].