Mitsubishi Electronics FX3S Garage Door Opener User Manual


 
718
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
33 Extension File Register Control – FNC290 to FNC299
33.2 FNC291 – SAVER / Save to ER
33.2 FNC291 – SAVER / Save to ER
Outline
This instruction writes the current values of the extension registers (R) stored in the PLC's built-in RAM to extension
file registers (ER) stored in a memory cassette (flash memory) in sector units (2048 points).
The RWER (FNC294) instruction provided in FX
3UC PLC Ver. 1.30 or later and FX3U PLC only writes (transfers) a
arbitrary number of points. It is not necessary to execute the INITR (FNC292) or the INITER (FNC295) instruction
when RWER instruction is used.
For RWER instruction, refer to Section 33.5.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (SAVER)
The contents (current values) of extension registers (R) specified by to +2047 are written (transferred) to
extension file registers (ER) inside a memory cassette (flash memory) with the same device numbers in “2048/n”
operation cycles (“2048/n+1” cycles if there is a remainder).
While the instruction is being executed, the number of points already written is stored in .
Operand Type Description Data Type
Head device number of extension register sector to which data is to be written
(Only the head device number of a sector of extension registers can be specified.)
16-bit binary
n Number of points written (transferred) in one operation cycle [0 n 2048]
Device number storing the number of already written points
Oper-
and
Type
Bit Devices Word Devices Others
System User Digit Specification System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
XYMTCSD
.b KnX KnY KnM KnS T C D R
U\G
V Z Modify K H E "
"P

n 

FNC 291
SAVER
Mnemonic Operation Condition
16-bit Instruction
7 steps
SAVER
Mnemonic Operation Condition
Continuous
Operation
32-bit Instruction
S
D
S
D
S
S
D
FNC291
SAVER
n
M

M8029
Instruction execution complete flag
Instruction execution complete
flag for SAVER instruction
Command
input
S
D
E
E +1
E +2
E +2047
+1
+2
+2047
Write
(transfer)
Extension file registers (ER)
inside memory cassette
Extension registers (R)
inside built-in RAM
*1
*1 “n” points are written (transferred) in each operation cycle.
S
S
S
S S
S
S
S