Honeywell EN2H-0221GE51 R0808 Heating System User Manual


 
SDC / DHC Operation
EN2H-0221GE51 R0808 99
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
Heat-
ing
circuit
name
Heating circuit
name
00000 ... ZZZZZ
* OEM
5.4.6 "Heat generator" menu (HEAT GENER.
The parameters in this menu refer to the type of the respective
heat generator and the associated specific control functions.
Para-
meter
Designation Setting range / Setting values Factory
setting
Setting
OFF Without heat generator 1
1 Oil/gas - one stage
2 Oil/gas - two stages
3 Oil/gas - 2 x one stage
4 Modulating burner
01 Design
5 Open Therm
OFF No start-up protection 1
1 Unlimited start-up
protection
2 Start-up protection
controlled by weather
conditions
02 Start-up protection
(not if parameter
01 = OFF)
3 Start-up protection
disconnected
03 Minimum tem-
perature limit (not
if parameter 01 =
OFF)
5°C to setting value of parameter
04
38 (5 with
automatic
operation)
04 Maximal
temperature limit
(not if parameter
01 = OFF)
Setting value of parameter 03 to
setting value of parameter 30
(OEM maximum limit)
80